Product Description:
Uninterruptible power supply with IQ technology for DIN rail mounting, input: 24 V DC, output: 24 V DC/5 A, including mounted universal DIN rail adapter UTA 107/30

GTIN
: 04046356554138
Series
: QUINT-UPS/24DC/24DC/5
Type
: Onderbrekingsvrije voeding
Key Features
- Uninterruptible power supply with IQ technology for DIN rail mounting
- input: 24 V DC
- output: 24 V DC/5 A
- including mounted universal DIN rail adapter UTA 107/30
Advantages
• Easy handling thanks to automatic battery detection, tool-free battery replacement during operation, and communication via the IFS interface
• Optimum use of the buffer time and preventive monitoring of the energy storage
• Rapid battery charging
• Comprehensive signaling and parameterization
• Fast tripping of standard circuit breakers with SFB (selective fuse breaking) technology
• Reliable starting of difficult loads with the static POWER BOOST power reserve with up to 1.5 times the nominal current permanently
Training Data Goes here
Dimensions
Width
35
Height
130
Depth
125
Width with alternative assembly
123
Height with alternative assembly
130
Depth with alternative assembly
39
Installation distance right/left
5 mm / 5 mm
Installation distance top/bottom
50 mm / 50 mm
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
≤ 95 % (25 °C, non-condensing)
Climatic class
3K3 (in acc. with EN 60721)
Input data
Input voltage
24
Nominal input voltage
24
Input voltage range
18 V DC ... 30 V DC
Current consumption (maximum)
9.4 A (maximum, mains operation)
Current consumption (charging process)
1.8 A (Charging, mains operation)
Fixed backup threshold
≤ 22 V DC
Variable connect threshold
1 V/0.1 s
Output data (24 V DC mains operation)
Nominal output voltage
24
Output voltage range (depends on the input voltage)
18 V DC ... 30 V DC
Nominal output current (IN)
5 A (-25 °C ... 60 °C)
POWER BOOST (IBoost)
7.5 A (-25°C ... 40°C)
Selective Fuse Breaking (ISFB)
30 A (-25 °C ... 60 °C)
Output data (24 V DC battery operation)
Output voltage range (depends on the input voltage)
19.2 V DC ... 27.6 V DC (UOUT = UBAT - 0,5 V DC)
Selective Fuse Breaking (ISFB)
32.5 A (-25 °C ... 60 °C)
General output data
Efficiency
> 98 % (Mains operation, with charged energy storage)
General
IQ technology
Yes
Net weight
0.5 kg
Protection class
III
MTBF (IEC 61709, SN 29500)
> 500000 h (25 °C)
MTBF (IEC 61709, SN 29500)
> 500000 h (40 °C)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
alignable: horizontal 5 mm, vertical 50 mm
Connection data, input
Connection method
Pluggable screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
20
Conductor cross section AWG max.
12
Stripping length
7
Screw thread
M4
Connection data for signaling
Conductor cross section AWG min.
24
Standards
EMC requirements for noise immunity
EN 61000-6-1
EMC requirements for noise immunity
EN 61000-6-2
EMC requirements for noise emission
EN 61000-6-3
EMC requirements for noise emission
EN 61000-6-4
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Rail applications
EN 50121-4
Conformance/approvals
UL approvals
UL Listed UL 508
UL approvals
UL/C-UL Recognized UL 60950-1
UL approvals
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
EMC data
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
Electrostatic discharge
EN 61000-4-2
Contact discharge
8 kV (Test Level 4)
Discharge in air
15 kV (Test Level 4)
Electromagnetic HF field
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
20
Frequency range
1 GHz ... 2 GHz
Test field strength
10
Frequency range
2 GHz ... 3 GHz
Test field strength
3
Comments
Criterion A
Fast transients (burst)
EN 61000-4-4
Input
2 kV (Test Level 3 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
Signal
2 kV (Test Level 4 - asymmetrical)
Surge voltage load (surge)
EN 61000-4-5
Input
1 kV (Test Level 2 - symmetrical)
Output
1 kV (Test Level 2 - symmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Conducted interference
EN 61000-4-6
I/O/S
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Voltage
10 V (Test Level 3)
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
EAC EAC-Zulassung
EAC RU*DE*08.B.01873/19
cULus Recognized
cULus Listed