Product Description:
Rail-mountable surge arrester as device protection for terminal equipment, fault signal in the plug and signaling contact in the base element, 2-section, pluggable. Design: 48 V DC

GTIN
: 04017918574987
Series
: PT 2+1-S-48DC
Type
: Overspanningsbeveiligingsmoduul Typ
Key Features
- Rail-mountable surge arrester as device protection for terminal equipment
- fault signal in the plug and signaling contact in the base element
- 2-section
- pluggable
- Design: 48 V DC
Advantages
• Easy testing and documentation with CHECKMASTER 2 with pluggable protective modules
• Maximum ease of maintenance thanks to the two-piece design
• Easy selection for all possible demands in MCR applications with a complete product portfolio
• The signal is not influenced during maintenance work, thanks to the impedance-neutral insertion and removal of protective plugs
• Permanent protective device monitoring with optical signaling via LED
Training Data Goes here
Dimensions
Height
90
Width
17.7 mm
Depth
65.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch
1
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 80 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % ... 95 %
General
EN type
T3
Number of ports
One
Mode of protection
L-N
Mode of protection
L-PE
Mode of protection
N-PE
Mode of protection
(L+) - (L-)
Mode of protection
(L+/L-) - PE
Mounting type
DIN rail: 35 mm
Color
jet black RAL 9005
Housing material
PA 6.6
Degree of pollution
2
Flammability rating according to UL 94
V-0
Type
DIN rail module, two-section, divisible
Surge protection fault message
Optical, remote indicator contact
Protective circuit
Nominal voltage UN
48
Maximum continuous voltage UC
60
Rated load current IL
26 A (30 °C)
Residual current IPE
≤ 10 µA
Nominal discharge current In (8/20) µs
500
Combination wave UOC
1 kV (2 Ω)
Combination wave UOC
6 kV (12 Ω)
Voltage protection level Up
≤ 120 V
Response time tA (L-N)
≤ 1 ns
Response time tA (L-PE)
≤ 1 ns
Short-circuit current rating ISCCR
200 A (without backup fuse for Uc)
Max. backup fuse with branch wiring
50 A (gG)
Maximum backup fuse for through wiring
25 A (gG)
Indicator/remote signaling
Switching function
N/C contact
Operating voltage
7 V DC ... 70 V DC (open collector)
Operating current
5 mA DC ... 15 mA (open collector)
Connection method
Screw connection
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section solid
0.2 mm² ... 4 mm²
Conductor cross section AWG
24 ... 12
Screw thread
M3
Tightening torque
0.8 Nm
Stripping length
8
Standards and Regulations
Standards/specifications
EN 61643-11 2012
Standards/specifications
IEC 61643-11 2011
Environmental Product Compliance
REACh SVHC
Hexahydromethylphthalic anhydride 25550-51-0
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
EAC EAC-Zulassung
EAC RU C-DE.*09.B.00169