Product Description:
Test terminal strip, nom. voltage: 400 V AC/DC, connection method: Push-in connection, number of connections: 24, number of positions: 12, cross section: 0.5 mm² - 10 mm², AWG: 20 - 8, width: 131.2 mm, height: 56.5 mm, color: gray, mounting type: Wall mounting

GTIN
: 04046356962148
Series
: PTWE 6-2/12
Type
: Teststekerstrook
Key Features
- Test terminal strip
- nom. voltage: 400 V AC/DC
- connection method: Push-in connection
- number of connections: 24
- number of positions: 12
- cross section: 0.5 mm² - 10 mm²
- AWG: 20 - 8
- width: 131.2 mm
- height: 56.5 mm
- color: gray
- mounting type: Wall mounting
Advantages
• Space saving, thanks to compact, modular test terminal strips
• Cost-effective, thanks to the tailored, modular design and use of standardized CLIPLINE complete accessories
• The integrated, robust switch contact is designed for the most stringent demands, and the use of high-quality materials ensures the transmission of signal currents, even after multiple actuations
• Maximum safety with leading and automatic transformer short circuit
Training Data Goes here
General
Number of positions
12
Number of levels
1
Number of connections
24
Potentials
12
Nominal cross section
6
Color
gray
Insulating material
PA
Flammability rating according to UL 94
V0
Rated surge voltage
4
Test surge voltage
5
Overvoltage category
III
Insulating material group
I
Maximum power dissipation for nominal condition
1.31 W
Maximum load current
30 A (with 6 mm² conductor cross section)
Nominal voltage UN
400 V AC/DC
Open side panel
No
Terminal block mounting
0.8 Nm ... 1 Nm
Shock protection test specification
DIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protection
guaranteed
Finger protection
guaranteed
Note regarding shock protection
When test disconnect plug is plugged in.
Result of surge voltage test
Test passed
Result of power-frequency withstand voltage test
Test passed
Power frequency withstand voltage setpoint
1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)
Test passed
Result of flexion and pull-out test
Test passed
Bending test rotation speed
10
Bending test turns
135
Bending test conductor cross section/weight
0.5 mm² / 0.3 kg
Bending test conductor cross section/weight
6 mm² / 1.4 kg
Tensile test result
Test passed
Result of tight fit on support
Test passed
Setpoint
5
Note
Dimensions panel cutout see appendix.
Result of voltage-drop test
Test passed
Result of temperature-rise test
Test passed
Requirement temperature-rise test
Increase in temperature ≤ 45 K
Note
From >5-pos., the derating curve should be used.
Short circuit stability result
Test passed
Conductor cross section short circuit testing
4
Short-time current
0.5 kA
Short-time current
0.3 kA
Short-time current
0.15 kA
Result of thermal test
Test passed
Proof of thermal characteristics (needle flame) effective duration
30
Result of aging test
Test passed
Ageing test for screwless modular terminal block temperature cycles
192
Note
The measuring transducer block is replaced every 100 cycles.
Oscillation, broadband noise test result
Test passed
Test specification, oscillation, broadband noise
DIN EN 50155 (VDE 0115-200):2008-03
Test spectrum
Service life test category 2, bogie-mounted
Test frequency
f1 = 5 Hz to f2 = 250 Hz
ASD level
6.12 (m/s2)2/Hz
Acceleration
3.12 g
Test duration per axis
5
Test directions
X-, Y- and Z-axis
Shock test result
Test passed
Test specification, shock test
DIN EN 50155 (VDE 0115-200):2008-03
Shock form
Half-sine
Acceleration
30g
Shock duration
18
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)
130
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
125
Static insulating material application in cold
-60 °C
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Calorimetric heat release NFPA 130 (ASTM E 1354)
27,5 MJ/kg
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Dimensions
Width
131.2 mm
Length
81
Height
56.5 mm
Plate thickness
1 mm ... 4 mm
Pitch
8.2 mm
Connection data
Connection
1
Connection method
Push-in connection
Stripping length
12
Connection in acc. with standard
IEC 60947-7-1
Conductor cross section solid min.
0.5 mm²
Conductor cross section solid max.
10
Conductor cross section AWG min.
20
Conductor cross section AWG max.
8
Conductor cross section flexible min.
0.5 mm²
Conductor cross section flexible max.
6
Min. AWG conductor cross section, flexible
20
Max. AWG conductor cross section, flexible
10
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
6
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.
6
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
0.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
1.5 mm²
Connection cross sections directly pluggable
1 mm² 10 mm²
Conductor cross section solid min.
1
Conductor cross section flexible, with ferrule without plastic sleeve min.
1
Conductor cross section flexible, with ferrule with plastic sleeve min.
1
Internal cylindrical gage
A5
Mounting
Mounting type
Wall mounting
Min. tightening torque of the mounting screw:
0.8 Nm
Max. tightening torque of the mounting screw:
1
Ambient conditions
Operating temperature
-60 °C ... 105 °C (max. short-term operating temperature 130°C)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
China RoHS
No hazardous substances above threshold values