Product Description:
Test plug, nom. voltage: 400 V, nominal current: 24 A, connection method: Screw connection, number of positions: 7, color: gray

GTIN
: 04055626379975
Series
: FTPC 6+1
Type
: Teststeker
Key Features
- Test plug
- nom. voltage: 400 V
- nominal current: 24 A
- connection method: Screw connection
- number of positions: 7
- color: gray
Advantages
• The robust test plug guarantees user-friendly handling and provides fixing options for the test cables to be connected
• The test blocks can be used universally for voltage transducers and current transformers
• The integrated, robust switch contact is designed for the most stringent demands, and the use of high-quality materials ensures the transmission of signal currents, even after multiple actuations
Training Data Goes here
General
Number of positions
7
Potentials
7
Nominal cross section
6
Color
gray
Insulating material
PA
Flammability rating according to UL 94
V0
Maximum load current
24
Maximum power dissipation for nominal condition
1.31 W
Nominal current IN
24
Nominal voltage UN
400
Shock protection test specification
DIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protection
guaranteed
Finger protection
guaranteed
Note regarding shock protection
When plugged in
Result of surge voltage test
Test passed
Result of power-frequency withstand voltage test
Test passed
Power frequency withstand voltage setpoint
1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)
Test passed
Result of flexion and pull-out test
Test passed
Bending test rotation speed
10
Bending test turns
135
Bending test conductor cross section/weight
0.2 mm² / 0.2 kg
Bending test conductor cross section/weight
6 mm² / 1.4 kg
Tensile test result
Test passed
Result of tight fit on support
Test passed
Tight fit on carrier
Panel cutout
Setpoint
5
Result of voltage-drop test
Test passed
Result of temperature-rise test
Test passed
Requirement temperature-rise test
Increase in temperature ≤ 45 K
Short circuit stability result
Test passed
Conductor cross section short circuit testing
4
Short-time current
300
Short-time current
500
Short-time current
1250
Note
The test with ...... mm² / .......A / ...s covers the equirements .......... mm² / ...... A / ...s acc. to IEC 60947-7-1:....-...
Result of thermal test
Test passed
Proof of thermal characteristics (needle flame) effective duration
30
Oscillation, broadband noise test result
Test passed
Test specification, oscillation, broadband noise
DIN EN 50155 (VDE 0115-200):2008-03
Test spectrum
Service life test category 1, class B, body mounted
Test frequency
f1 = 5 Hz to f2 = 150 Hz
ASD level
1.857 (m/s2)2/Hz
Acceleration
0,8 g
Test duration per axis
5
Test directions
X-, Y- and Z-axis
Shock test result
Test passed
Test specification, shock test
DIN EN 50155 (VDE 0115-200):2008-03
Shock form
Half-sine
Acceleration
5g
Shock duration
30
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)
130
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
125
Static insulating material application in cold
-60 °C
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Calorimetric heat release NFPA 130 (ASTM E 1354)
27,5 MJ/kg
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Dimensions
Pitch
8.2 mm
Connection data
Note
The conductor cross section depends on the cable lug used
Connection method
Screw connection
Conductor cross section flexible min.
0.5 mm²
Conductor cross section flexible max.
2.5 mm²
Min. AWG conductor cross section, flexible
20
Max. AWG conductor cross section, flexible
14
Mounting
Min. tightening torque of the test socket screw:
0.5 Nm
Max. tightening torque of the test socket screw:
0.6 Nm
Ambient conditions
Operating temperature
-60 °C ... 105 °C (max. short-term operating temperature 130°C)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C