Product Description:
Test disconnect terminal block, with slide, connection method: Screw connection, cross section: 0.5 mm² - 10 mm² , AWG: 20 - 10, width: 8.2 mm, mounting type: NS 35/7,5, NS 35/15, NS 32, color: blue

GTIN
: 04046356576796
Series
: URTK/SP BU
Type
: Meettransformator-scheidingsklem
Key Features
- Test d.sconnect terminal block
- with slide
- connection method: Screw connection
- cross section: 0.5 mm² - 10 mm²
- AWG: 20 - 10
- width: 8.2 mm
- mounting type: NS 35/7
- NS 35/15
- NS 32
- color: blue
Training Data Goes here
General
Number of levels
1
Number of connections
2
Potentials
1
Nominal cross section
6
Color
blue
Insulating material
PA
Flammability rating according to UL 94
V0
Rated surge voltage
6
Degree of pollution
3
Overvoltage category
III
Insulating material group
I
Maximum power dissipation for nominal condition
1.31 W
Maximum load current
50 A (with 10 mm² conductor cross section)
Nominal current IN
41
Nominal voltage UN
500
Open side panel
No
Relative insulation material temperature index (Elec., UL 746 B)
130
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
130
Static insulating material application in cold
-60 °C
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Calorimetric heat release NFPA 130 (ASTM E 1354)
28
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Dimensions
Width
8.2 mm
Length
99.5 mm
Height NS 35/7,5
59
Height NS 35/15
66.5 mm
Height NS 32
64
Connection data
Note
Terminal point
Connection
1
Connection method
Screw connection
Screw thread
M4
Stripping length
11
Tightening torque, min
1.5 Nm
Tightening torque max
1.8 Nm
Connection in acc. with standard
IEC 60947-7-1
Conductor cross section solid min.
0.5 mm²
Conductor cross section solid max.
10
Conductor cross section AWG min.
20
Conductor cross section AWG max.
8
Conductor cross section flexible min.
0.5 mm²
Conductor cross section flexible max.
6
Min. AWG conductor cross section, flexible
20
Max. AWG conductor cross section, flexible
10
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
6
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.
6
2 conductors with same cross section, solid min.
0.5 mm²
2 conductors with same cross section, solid max.
2.5 mm²
2 conductors with same cross section, stranded min.
0.5 mm²
2 conductors with same cross section, stranded max.
4
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
0.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
4
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
0.5 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
2.5 mm²
Ambient conditions
Operating temperature
-60 °C ... 105 °C (max. short-term operating temperature 130°C)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Standards and Regulations
Connection in acc. with standard
CSA
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50 years