Product Description:
Feed-through terminal block with bolt connection method, cross section: 0.1 - 6 mm², AWG: 26 - 10, width 13 mm, color: gray

GTIN
: 04046356500364
Series
: RBO 5-T-F
Type
: Meettransformator-scheidingsklem
Key Features
- Feed-through terminal block with bolt connection method
- cross section: 0.1 - 6 mm²
- AWG: 26 - 10
- width 13 mm
- color: gray
Advantages
• Connection screws with 4 mm test connection
Training Data Goes here
General
Number of levels
1
Number of connections
2
Potentials
1
Nominal cross section
10
Color
gray
Insulating material
PA
Flammability rating according to UL 94
V0
Rated surge voltage
8
Degree of pollution
3
Overvoltage category
III
Insulating material group
I
Maximum power dissipation for nominal condition
1.82 W
Maximum load current
50 A (with 10 mm² conductor cross section)
Nominal current IN
50
Nominal voltage UN
800 V (with open 630 V disconnect point)
Open side panel
Yes
Result of surge voltage test
Test passed
Result of power-frequency withstand voltage test
Test passed
Power frequency withstand voltage setpoint
2
Result of voltage-drop test
Test passed
Result of temperature-rise test
Test passed
Requirement temperature-rise test
Increase in temperature ≤ 45 K
Short circuit stability result
Test passed
Conductor cross section short circuit testing
10
Short-time current
1.2 kA
Oscillation, broadband noise test result
Test passed
Test specification, oscillation, broadband noise
DIN EN 50155 (VDE 0115-200):2008-03
Test spectrum
Service life test category 1, class B, body mounted
Test frequency
f1 = 5 Hz to f2 = 150 Hz
ASD level
0.02 g²/Hz
Acceleration
0,8 g
Test duration per axis
5
Test directions
X-, Y- and Z-axis
Shock test result
Test passed
Test specification, shock test
DIN EN 50155 (VDE 0115-200):2008-03
Shock form
Half-sine
Acceleration
5g
Shock duration
30
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)
130
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
130
Static insulating material application in cold
-60 °C
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Calorimetric heat release NFPA 130 (ASTM E 1354)
28
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Dimensions
Width
13
End cover width
10
Length
79.9 mm
Height
39.7 mm
Pitch
13
Connection data
Connection
1
Connection method
Bolt connection
Stripping length
The stripping length depends on the specification provided by the cable lug manufacturer.
Connection in acc. with standard
IEC 60947-7-1
Cable lug connection according to standard
DIN 46234:1980-03
Min. cross section for cable lug connection
0.1 mm²
Max. cross section for cable lug connection
10
AWG min
26
AWG max
8
Hole diameter, min.
5.3 mm
Cable lug width, max.
10
Bolt diameter
5
Screw thread
M5
Tightening torque, min
2
Tightening torque max
2.2 Nm
Cable lug connection according to standard
DIN 46237:1970-07
Min. cross section for cable lug connection
0.5 mm²
Max. cross section for cable lug connection
6
AWG min
20
AWG max
10
Ambient conditions
Operating temperature
-60 °C ... 105 °C (max. short-term operating temperature 130°C)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Standards and Regulations
Connection in acc. with standard
UL
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
EAC RU C-DE.BL08.B.00540