Product Description:
Protective plug PT with HF protective circuit for two 2-core floating signal circuits. Nominal voltage: 24 V DC

GTIN
: 04017918607210
Series
: PT 2X2-HF-24 DC-ST
Type
: Overspanningsbeveiligingssteker
Key Features
- Protective plug PT with HF protective circuit for two 2-core floating signal circuits
- Nominal voltage: 24 V DC
Advantages
• Easy testing and documentation with CHECKMASTER 2 with pluggable protective modules
• Maximum ease of maintenance thanks to the two-piece design
• Easy selection for all possible demands in MCR applications with a complete product portfolio
• The signal is not influenced during maintenance work, thanks to the impedance-neutral insertion and removal of protective plugs
Training Data Goes here
Dimensions
Height
45
Width
17.7 mm
Depth
52
Horizontal pitch
1
Ambient conditions
Ambient temperature (operation)
-40 °C ... 85 °C
Degree of protection
IP20
General
Housing material
PA
Flammability rating according to UL 94
V-0
Color
black
Standards for cearances and creepage distances
DIN VDE 0110-1
Standards for cearances and creepage distances
IEC 60664-1
Mounting type
on base element
Type
Male
Number of positions
5
Direction of action
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Arrester can be tested with CHECKMASTER from software version:
From SW rev. 1.00
Protective circuit
IEC test classification
C1
IEC test classification
C2
IEC test classification
C3
IEC test classification
D1
VDE requirement class
C1
VDE requirement class
C2
VDE requirement class
C3
VDE requirement class
D1
Nominal voltage UN
24
Maximum continuous voltage UC
28
Maximum continuous voltage UC
19.8 V AC
Rated current
450 mA (45 °C)
Operating effective current IC at UC
≤ 5 µA
Residual current IPE
≤ 4 µA (with PT 2X2-BE)
Residual current IPE
≤ 1 µA (with PT 2X2+F-BE)
Nominal discharge current In (8/20) µs (line-line)
10
Nominal discharge current In (8/20) µs (line-earth)
10
Pulse discharge current Iimp (10/350) µs
2.5 kA
Total discharge current Itotal (8/20) µs
20
Max. discharge current Imax (8/20) µs maximum (line-line)
10
Max. discharge current Imax (8/20) µs maximum (line-earth)
10
Nominal pulse current Ian (10/1000) µs (line-line)
30
Output voltage limitation at 1 kV/µs (line-line) spike
≤ 120 V
Output voltage limitation at 1 kV/µs (line-earth) spike
≤ 450 V
Output voltage limitation at 1 kV/µs (line-earth) spike
≤ 1 kV (with PT 2X2+F-BE)
Output voltage limitation at 1 kV/µs (line-line) static
≤ 45 V
Output voltage limitation at 1 kV/µs (line-signalground) static
≤ 450 V
Residual voltage at In (line-line)
≤ 40 V
Residual voltage with Ian (10/1000) µs (line-line)
≤ 50 V
Voltage protection level Up (line-line)
≤ 120 V (C2 - 10 kV / 5 kA)
Voltage protection level Up (line-earth)
≤ 450 V (C2 - 10 kV / 5 kA)
Response time tA (line-line)
≤ 500 ns
Response time tA (line-earth)
≤ 500 ns
Input attenuation aE, sym.
0.2 dB (≤ 5 MHz)
Input attenuation aE, asym.
----
Cut-off frequency fg (3 dB), sym. in 100 Ω system
typ. 70 MHz
Capacity (line-line)
typ. 30 pF
Resistance per path
2.2 Ω
Surge protection fault message
none
Max. required back-up fuse
500 mA (T)
Impulse durability (line-line)
C2 - 10 kV / 5 kA
Impulse durability (line-earth)
C2 - 10 kV / 5 kA
Impulse durability (line-earth)
D1 - 2.5 kA
Connection data
Connection method
Screw connection (in connection with the base element)
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section solid
0.2 mm² ... 4 mm²
Conductor cross section AWG
24 ... 12
Standards and Regulations
Standards/regulations
IEC 61643-21
Standards/specifications
IEC 61643-21 2000
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
EAC EAC-Zulassung
EAC RU C-DE.*09.B.00169
cULus Listed
Test report from "Keymile" regarding the qualification of surge protection from Phoenix Contact on ADSL and ADSL2+ (pdf110 KB)
LinkTest report from "Keymile" regarding the qualification of surge protection from Phoenix Contact on ADSL and ADSL2+ (pdf107 KB)
Link