Product Description:
Protective plug PT with protective circuit for higher signal voltages, 2-channel, visual error warning. Nominal voltage: 230 V AC

GTIN
: 04017918182854
Series
: PT 2X1VA-230AC-ST
Type
: Overspanningsbeveiligingssteker
Key Features
- Protective plug PT with protective circuit for higher signal voltages
- 2-channel
- visual error warning
- Nominal voltage: 230 V AC
Advantages
• Easy testing and documentation with CHECKMASTER 2 with pluggable protective modules
• Maximum ease of maintenance thanks to the two-piece design
• Easy selection for all possible demands in MCR applications with a complete product portfolio
• The signal is not influenced during maintenance work, thanks to the impedance-neutral insertion and removal of protective plugs
Training Data Goes here
Dimensions
Height
44.8 mm
Width
17.5 mm
Depth
51.7 mm
Horizontal pitch
1
Complete module height
90
Complete module width
17.7 mm
Complete module depth
65.5 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 85 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Degree of protection
IP20
General
Housing material
PA 6.6
Flammability rating according to UL 94
V-0
Color
jet black RAL 9005
Mounting type
on base element
Type
Male
Direction of action
Line-Line & Line-Earth Ground
Arrester can be tested with CHECKMASTER from software version:
From SW rev. 1.00
Additional descriptions
Note
Technical data is valid in association with the following specified base elements:
Note
PT -BE/ FM 2839282
Protective circuit
IEC test classification
C1
IEC test classification
C2
IEC test classification
C3
IEC test classification
D1
Nominal voltage UN
230 V AC (50/60 Hz)
Maximum continuous voltage UC
275
Maximum continuous voltage UC
275 V AC (50/60 Hz)
Rated current
26 A AC (30 °C)
Rated current
1 A DC (82 °C)
Operating effective current IC at UC
≤ 1.5 mA AC
Operating effective current IC at UC
≤ 2 mA DC
Residual current IPE
≤ 3 mA AC
Residual current IPE
≤ 4 mA DC
Nominal discharge current In (8/20) µs (line-earth)
2.5 kA
Pulse discharge current Iimp (10/350) µs
500
Total discharge current Itotal (8/20) µs
5
Output voltage limitation at 1 kV/µs (line-earth) spike
≤ 650 V
Output voltage limitation at 1 kV/µs (line-earth) static
≤ 650 V
Voltage protection level Up (line-earth)
≤ 750 V (C1 - 1.4 kV / 0.7 kA)
Voltage protection level Up (line-earth)
≤ 900 V (C2 - 5 kV/2,5 kA)
Voltage protection level Up (line-earth)
≤ 750 V (C3 - 100 A)
Response time tA (line-earth)
≤ 25 ns
Input attenuation aE, asym.
typ. 0.3 dB (≤ 650 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (signal ground) in 150 Ω system
typ. 2.2 MHz
Capacity (line-earth)
typ. 1 nF
Surge protection fault message
optical
Max. required back-up fuse
25 A AC (gL/gG)
Max. required back-up fuse
1 A DC (T)
Impulse durability (line-earth)
C1 - 1,4 kV / 0,7 kA
Impulse durability (line-earth)
C2 - 5 kV / 2.5 kA
Impulse durability (line-earth)
C3 - 100 A
Impulse durability (line-earth)
D1 - 500 A
Connection data
Connection method
Screw connection (in connection with the base element)
Screw thread
M3
Tightening torque
0.5 Nm
Stripping length
8
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section solid
0.2 mm² ... 4 mm²
Conductor cross section AWG
24 ... 12
Standards and Regulations
Standards/specifications
IEC 61643 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
Standards/specifications
EN 61643-21 2001 + A1:2009 + A2:2013
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years