Product Description:
LSA-PLUS plug (COMTRAB CT 10) with surge protection incl. visual fault warning for nine 2-core signal circuits. Nominal voltage: 230 V AC. Design: 10 double wires

GTIN
: 04017918106553
Series
: CT 10-9VA-230AC
Type
: Overspanningsbeveiligingssteker
Key Features
- LSA-PLUS plug with surge protection incl. visual fault warning for nine 2-core signal circuits. Nominal voltage: 230 V AC. Design: 10 double wires
Advantages
• Space-saving due to compact design
• Flexible fields of application with modular protective plug
• Can be used in LSA-PLUS disconnect and control strips or CT-TERMIBLOCK via adapted connection technology
Training Data Goes here
Dimensions
Height
22
Width
111
Depth
68.5 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 85 °C
Altitude
≤ 2000 mm (amsl (above mean sea level))
Degree of protection
IP20
General
Housing material
PBT
Flammability rating according to UL 94
V-0
Color
jet black RAL 9005
Standards for cearances and creepage distances
VDE 0110-1
Standards for cearances and creepage distances
IEC 60664
Mounting type
On CT-TERMIBLOCK and LSA-PLUS disconnect strip
Type
LSA-PLUS module
Direction of action
Line-Line & Line-Earth Ground
Arrester can be tested with CHECKMASTER from software version:
From SW rev. 1.00
Protective circuit
IEC test classification
C1
IEC test classification
C3
Nominal voltage UN
250
Nominal voltage UN
230
Maximum continuous voltage UC
275
Rated current
1.5 A AC (per path)
Rated current
200 mA DC (per path)
Operating effective current IC at UC
≤ 1.5 mA AC (per path)
Operating effective current IC at UC
≤ 2 mA DC (per path)
Residual current IPE
≤ 1 µA
Nominal discharge current In (8/20) µs (line-earth)
1.5 kA
Nominal discharge current In (8/20) µs (line-signal ground)
1.5 kA
Nominal discharge current In (8/20) µs (signalground-earth)
5
Total discharge current Itotal (8/20) µs
5
Max. discharge current Imax (8/20) µs maximum (line-earth)
5 kA (10-PE)
Max. discharge current Imax (8/20) µs maximum (line-signalground)
3
Residual voltage at In (line-earth)
≤ 1.4 kV
Residual voltage at In (line-signalground)
≤ 1.1 kV
Fixed cable length
10
Voltage protection level Up (line-earth)
≤ 1.4 kV (10-PE)
Voltage protection level Up (line-signalground)
≤ 1.1 kV
Response time tA (line-line)
≤ 25 ns
Response time tA (line-signalground)
≤ 25 ns
Response time tA (line-earth)
≤ 100 ns
Frequency range
50 Hz ... 60 Hz
Capacity (line-signalground)
typ. 320 pF
Capacity (line-earth)
typ. 2 pF (10-PE)
Surge protection fault message
none
Max. required back-up fuse
1.5 A AC (gL)
Max. required back-up fuse
200 mA DC (F)
Impulse durability (line-earth)
C2 - 3 kV/1.5 kA
Impulse durability (line-signalground)
C2 - 3 kV/1.5 kA
Impulse durability (signalground-earth)
C2 - 10 kV/5 kA
Connection data
Connection method
can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips
Connection method IN
COMTRAB plug-in system
Connection method OUT
COMTRAB plug-in system
Standards and Regulations
Standards/specifications
IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
Standards/specifications
EN 61643-21 2001 + A1:2009 + A2:2013
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
There is no certificate available for this product.