Product Description:
Attachment connector with surge protection for LAN interfaces. Connection: RJ45 sockets

GTIN
: 04017918172275
Series
: D-LAN-A/RJ45-BS
Type
: Overspanningsbeveiligingsmoduul
Key Features
- Attachment connector with surge protection for LAN interfaces
- Connection: RJ45 sockets
Training Data Goes here
Ambient conditions
Ambient temperature (operation)
-40 °C ... 80 °C
Degree of protection
IP20
General
Color
black
Standards for cearances and creepage distances
DIN VDE 0110-1
Standards for cearances and creepage distances
IEC 60664-1
Overvoltage category
II
Degree of pollution
2
Type
Attachment plug
Direction of action
Line-Line & Line-Shield & Shield-Earth Ground
Protective circuit
IEC test classification
C1
IEC test classification
C2
IEC test classification
C3
IEC test classification
B2
VDE requirement class
C1
VDE requirement class
C2
VDE requirement class
C3
VDE requirement class
B2
Maximum continuous voltage UC
± 11 V DC
Nominal current IN
1.5 A (25 °C)
Operating effective current IC at UC
≤ 1 mA
Residual current IPE
≤ 1 µA
Nominal discharge current In (8/20) µs (line-line)
350
Nominal discharge current In (8/20) µs (line-earth)
2.5 kA
Max. discharge current Imax (8/20) µs maximum (line-line)
350
Max. discharge current Imax (8/20) µs maximum (line-earth)
2.5 kA
Nominal pulse current Ian (10/700) µs (line-line)
160
Nominal pulse current Ian (10/700) µs (line-earth)
160
Output voltage limitation at 1 kV/µs (line-line) static
≤ 30 V
Output voltage limitation at 1 kV/µs (line-earth) static
≤ 500 V
Output voltage limitation (10/700) µs (line-line)
≤ 12 V
Output voltage limitation (10/700) µs (line-earth)
≤ 200 V
Residual voltage at In (line-line)
≤ 37 V
Residual voltage at In (line-earth)
≤ 70 V
Voltage protection level Up (line-line)
≤ 30 V (C1 - 500 V / 250 A)
Voltage protection level Up (line-line)
≤ 10 V (B2 - 4 kV / 100 A)
Voltage protection level Up (line-earth)
≤ 400 V (C1 - 500 V / 250 A)
Voltage protection level Up (line-earth)
≤ 150 V (B2 - 4 kV / 100 A)
Voltage protection level Up (shield-earth)
≤ 600 V (C2 - 4 kV / 2 kA)
Response time tA (line-line)
≤ 500 ns
Response time tA (line-earth)
≤ 100 ns
Input attenuation aE, asym.
1 dB (up to 100 MHz, 100 Ω system)
Near-end crosstalk attenuation
35 dB (pair 3-6 against pair 4-5 in 100 Ω system / 100 MHz)
Cut-off frequency fg (3 dB), sym. in 100 Ω system
> 100 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ω system
> 100 MHz
Capacity (line-line)
20 pF (1 MHz)
Capacity (line-earth)
1 pF (1 MHz)
Surge protection fault message
none
Connection data
Connection method
RJ45
Connection method IN
RJ45 socket
Connection method OUT
RJ45 socket
Connection technology
Network interfaces (e.g. Ethernet, Token Ring and CDDI/FDDI)
Standards and Regulations
Standards/regulations
IEC 61643-21
Standards/regulations
EN 50173
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
EAC RU C-DE.*09.B.00169