Product Description:
19 rack with 24 surge protected ports for data interfaces in Ethernet (1000Base-T), Token Ring and FDDI/CDDI networks in acc. with Class D/EN 50173 (CAT5e), connection on the protective device: RJ45 sockets

GTIN
: 04017918959968
Series
: D-LAN-19i-24
Type
: Overspanningsbeveiligingsmoduul
Key Features
- 19 rack with 24 surge protected ports for data interfaces in Ethernet
- Token Ring and FDDI/CDDI networks in acc. with Class D/EN 50173
- connection on the protective device: RJ45 sockets
Advantages
• Space saving with low installed height˽(1RU)
• Easy network integration via RJ45 jacks
• Can be used in applications up to 1˽Gbps with adapted protective circuit
• Easy to extend with the modular design
Training Data Goes here
Dimensions
Height
44
Width
483
Depth
160
Height unit
1
Ambient conditions
Ambient temperature (operation)
-40 °C ... 80 °C
Degree of protection
IP20
General
Housing material
Sheet steel
Color
beige
Standards for cearances and creepage distances
DIN VDE 0110-1
Standards for cearances and creepage distances
IEC 60664-1
Overvoltage category
II
Degree of pollution
2
Mounting type
19" rack
Type
19" rack patch module
Number of positions
24
Direction of action
Line-Line & Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground
Protective circuit
IEC test classification
C1
IEC test classification
C2
IEC test classification
C3
IEC test classification
B3
Maximum continuous voltage UC
6
Rated current
1.5 A (25 °C)
Operating effective current IC at UC
≤ 1 mA
Residual current IPE
≤ 1 mA (jumper 2 unplugged)
Nominal discharge current In (8/20) µs (line-line)
350
Nominal discharge current In (8/20) µs (line-earth)
350
Nominal discharge current In (8/20) µs (shield-earth)
2.5 kA (with insulated housing)
Total discharge current Itotal (8/20) µs
10
Max. discharge current Imax (8/20) µs maximum (line-earth)
----
Nominal pulse current Ian (10/1000) µs (line-line)
100
Nominal pulse current Ian (10/1000) µs (line-earth)
100
Output voltage limitation at 1 kV/µs (line-line) static
≤ 20 V
Output voltage limitation at 1 kV/µs (line-earth) static
≤ 30 V (J2 plugged)
Output voltage limitation at 1 kV/µs (line-earth) static
≤ 170 V (J2 unplugged)
Output voltage limitation at 1 kV/µs (shield-earth) static
≤ 700 V (with insulated shield)
Residual voltage at In (line-line)
≤ 65 V
Residual voltage at In (line-earth)
≤ 45 V (J2 ON)
Residual voltage at In (line-earth)
≤ 220 V (J2 OFF)
Residual voltage at In (shield-earth)
≤ 700 V
Voltage protection level Up (line-line)
≤ 50 V (C1 - 500 V / 250 A)
Voltage protection level Up (line-earth)
≤ 40 V (C1 - 500 V / 250 A (J2 ON))
Voltage protection level Up (line-earth)
≤ 180 V (C1 - 500 V / 250 A (J2 OFF))
Voltage protection level Up (shield-earth)
≤ 800 V (with insulated housing)
Response time tA (line-line)
≤ 1 ns
Response time tA (line-earth)
≤ 1 ns
Response time tA (line-shield)
≤ 100 ns
Input attenuation aE, sym.
typ. 1 dB (≤ 100 MHz)
Input attenuation aE, asym.
----
Near-end crosstalk attenuation
typ. 36 dB (100 Ω system / 100 MHz)
Cut-off frequency fg (3 dB), sym. in 100 Ω system
> 100 MHz
Capacity (line-line)
typ. 20 pF
Capacity (line-earth)
typ. 1 pF
Surge protection fault message
none
Impulse durability (line-line)
C1 - 500 V / 250 A
Impulse durability (line-earth)
C1 - 500 V / 250 A
Impulse durability (shield-earth)
C2 - 4 kV/2 kA
Connection data
Connection method
RJ45
Connection method IN
RJ45 socket
Connection method OUT
RJ45 socket
Connection technology
Network interfaces (e.g. Ethernet, Token Ring and CDDI/FDDI)
Standards and Regulations
Standards/regulations
IEC 61643-21
Standards/regulations
DIN EN 50173-1
Standards/specifications
IEC 61643-21 2000
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
China RoHS
No hazardous substances above threshold values
EAC RU C-DE.*09.B.00169
Testing in acc. with Class D, EN 50173-1 (pdf163 KB)
Link