Product Description:
MCR repeater power supply with HART transmission, input signal 4...20 mA, output signal 4...20 mA, with screw connection.

GTIN
: 04046356046428
Series
: MINI MCR-SL-RPSS-I-I
Type
: Voedingsscheidingsmoduul
Key Features
- MCR repeater power supply with HART transmission
- input signal 4...20 mA
- output signal 4...20 mA
- with screw connection.
Advantages
• Bidirectional HART transmission as an option
• Power supply possible via the foot element (TBUS)
• Can be used as an isolator with passive input
• Highly-compact repeater power supplies for electrical isolation, amplification, and filtering of standard analog signals
• Supply of 2-conductor and passive 3-conductor sensors
• 3-way isolation
Training Data Goes here
Dimensions
Width
6.2 mm
Height
93.1 mm
Depth
101.2 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Degree of protection
IP20
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Input data
Description of the input
Current input (sensor circuit)
Number of inputs
1
Current input signal
4 mA ... 20 mA (repeater power supply and isolator operation)
Current input signal
0 mA ... 20 mA (isolator operation)
Max. input current
28
Input resistance current input
approx. 50 Ω
Transmitter supply voltage
16.5 V
Output data
Output name
Current output
Number of outputs
1
Current output signal
4 mA ... 20 mA (repeater power supply and isolator operation)
Current output signal
0 mA ... 20 mA (isolator operation)
Max. output current
> 21 mA (22.5 mA, typical)
Load/output load current output
≤ 500 Ω (I = 20 mA)
Ripple
< 20 mVrms (at 500 Ω)
Transmission Behavior
1:1 to input signal
Power supply
Nominal supply voltage
24
Supply voltage range
20.4 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Power consumption
< 900 mW (at 24 V DC and in repeater power supply operation)
Power consumption
< 600 mW (at 24 V DC and in isolator operation)
Connection data
Connection method
Screw connection
Stripping length
12
Screw thread
M3
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
26 ... 12
General
No. of channels
1
Maximum transmission error
≤ 0.2 % (of final value)
Transmission error, typical
≤ 0.1 % (of final value)
Maximum temperature coefficient
< 0.005 %/K
Temperature coefficient, typical
< 0.002 %/K
Limit frequency (3 dB)
175 Hz (typ.)
Step response (10-90%)
< 2 ms (typ.)
Protective circuit
Transient protection
Electrical isolation
Basic insulation according to EN 61010
Overvoltage category
II
Degree of pollution
2
Rated insulation voltage
50 V AC/DC
Test voltage, input/output/supply
1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Color
green
Housing material
PBT
Mounting position
any
Assembly instructions
To bridge the supply voltage, the DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used. It can be snapped onto a 35 mm DIN rail according to EN 60715.
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
Data communication (bypass)
Limit frequency (3 dB)
approx. 2.5 Hz
EMC data
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
3
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Standards and Regulations
Standards/regulations
EN 61000-4-2
Standards/regulations
EN 61000-4-5
Conformance/approvals
Designation
CE
Certificate
----
Designation
UL, USA/Canada
Identification
UL 508 Listed
Identification
Class I, Div. 2, Groups A, B, C, D T4
Identification
Class I, Zone 2, Group IIC
Designation
Shipbuilding approval
Certificate
DNV GL TAA00000N1
Temperature
B
Humidity
B
Vibration
B
EMC
A
Enclosure
A
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years