Panel feed-through terminal block, connection method: Screw connection with tension sleeve, Screw connection with tension sleeve, number of positions: 1, load current: 232 A, cross section: 25 mm² - 95 mm², connection direction of the conductor to plug-in direction: 0 °, width: 25 mm, color: gray
GTIN
: 04017918117047
Series
: HDFK 95
Type
: Doorvoerklem
Key Features
- Panel feed-through terminal block
- connection method: Screw connection with tension sleeve
- Screw connection with tension sleeve
- number of positions: 1
- load current: 232 A
- cross section: 25 mm² - 95 mm²
- connection direction of the conductor to plug-in direction: 0 °
- width: 25 mm
- color: gray
Advantages
• Well-known connection principle allows worldwide use
• Low temperature rise, thanks to maximum contact force
• Tool-free snap-in principle enables easy mounting on the device panel
• Automatic panel thickness compensation enables universal use
Training Data Goes here
Item properties
Brief article description
Panel feed-through terminal block
Range of articles
HDFK 95
Pitch
25
Number of positions
1
Number of connections
2
Number of potentials
1
Electrical parameters
Nominal current
232
Nom. voltage
1000 V (With metal panels of 1 mm ... 2.5 mm)
Maximum load current
232 A (with 95 mm² conductor cross section)
Rated voltage (III/3)
1000
Rated surge voltage (III/3)
8
Connection capacity, external
Connection method
Screw connection with tension sleeve
Connection direction of the conductor to plug-in direction
0
Conductor cross section solid
25 mm² ... 95 mm²
Conductor cross section flexible
35 mm² ... 95 mm²
Conductor cross section flexible, with ferrule without plastic sleeve
25 mm² ... 95 mm²
Conductor cross section, flexible, with ferrule, with plastic sleeve
25 mm² ... 95 mm²
2 conductors with same cross section, solid
16 mm² ... 35 mm²
2 conductors with same cross section, flexible
16 mm² ... 35 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve
16 mm² ... 35 mm²
Internal cylindrical gage
B12
Stripping length
27
Torque
15 Nm ... 20 Nm
Material data - contact
Note
WEEE/RoHS-compliant, free of whiskers according to IEC 60068-2-82/JEDEC JESD 201
Contact material
Cu alloy
Surface characteristics
tin-plated
Material data - housing
Housing color
gray (7042)
Insulating material
PA
Insulating material group
I
CTI according to IEC 60112
600
Flammability rating according to UL 94
V0
Glow wire flammability index GWFI according to EN 60695-2-12
850
Glow wire ignition temperature GWIT according to EN 60695-2-13
775
Temperature for the ball pressure test according to EN 60695-10-2
125
Dimensions for the product
Dimensional drawing
----
Caption
Schematische Abbildung - weitere Details siehe Produktfamilienzeichnung im Download Center
Length [ l ]
95.4 mm
Width [ w ]
25
Height [ h ]
74
Dimensions for mounting cutout
Plate thickness
1 mm ... 6 mm
Packaging information
Type of packaging
packed in cardboard
Pieces per package
10
Denomination packing units
Pcs.
General product information
Type of note
Notes on safety
Note
The cable entry funnel is not touch-proof. Never connect or disconnect the terminal when it is energized. Take appropriate steps to ensure touch proofness.
Termination and connection method
Test for conductor damage and slackening
IEC 60947-7-1:2009-04
Test for conductor damage and slackening
Test passed
Pull-out test
Pull-out test
IEC 60947-7-1:2009-04
Conductor cross section / conductor type / tensile force
25 mm² / stranded / > 135 N
Conductor cross section / conductor type / tensile force
35 mm² / flexible / > 190 N
Conductor cross section / conductor type / tensile force
95 mm² / stranded / > 351 N
Conductor cross section / conductor type / tensile force
95 mm² / flexible / > 351 N
Mechanical tests according to standard
Test specification
IEC 60947-7-1 (in parts)
Electrical tests
Rated current
232
Conductor cross section
95
Air clearances and creepage distances
Clearances and creepage distances
Metal wall 1.0 mm ... 2.5 mm IEC 60947-7-1:2009-04
Application
Metal wall 1.0 mm ... 2.5 mm
Specification
IEC 60947-7-1:2009-04
Minimum clearance - inhomogeneous field (III/3)
8
Minimum creepage distance value (III/3)
12.5 mm
Temperature-rise test
Requirement temperature-rise test
Increase in temperature ≤ 45 K
Standards and Regulations
Connection in acc. with standard
CSA
Connection in acc. with standard
IEC 60947-7-1
Safety note
• Only electrically qualified personnel may install and operate the product.To recognize and prevent danger, the qualified personnel must be familiar with the basics of electrical engineering.
Safety note
• Observe the technical data provided here and refer to the documents listed under “Downloads”. The download area contains important information, such as installation notes, technical drawings, and 3D data.
Safety note
• The cable entry funnel is not safe to touch. Never connect or disconnect the terminal when it is energized. Take appropriate steps to ensure touch protection.
Glow-wire test
Specification
IEC 60695-2-11:2000-10
Temperature
960
Time of exposure
30
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years