Product Description:
N disconnect terminal block, for neutral conductor disconnection, Screw connection, cross section: 0.2 mm² - 10 mm², AWG: 24 - 8, width: 8.2 mm, color: blue, mounting type: NS 35/7,5, NS 35/15

GTIN
: 04046356299022
Series
: UTN 6
Type
: Nulscheidingsklem
Key Features
- N disco.nect terminal block
- for neutral conductor disconnection
- Screw connection
- cross section: 0.2 mm² - 10 mm²
- AWG: 24 - 8
- width: 8.2 mm
- color: blue
- mounting type: NS 35/7
- NS 35/15
Advantages
• Same shape as UT standard terminal blocks
Training Data Goes here
General
Note
Assembly instruction:In order to securely fix the neutral busbar in place, support brackets must be placed at the beginning and end of each terminal strip as well as every 20 cm on longer terminal strips.The corresponding support brackets can be found at phoenixcontact.net/products
Number of levels
1
Number of connections
1
Potentials
1
Nominal cross section
6
Color
blue
Insulating material
PA
Flammability rating according to UL 94
V0
Maximum load current
41
Rated surge voltage
6
Degree of pollution
3
Overvoltage category
III
Insulating material group
I
Maximum power dissipation for nominal condition
1.31 W
Nominal current IN
41
Nominal voltage UN
400
Open side panel
Yes
Shock protection test specification
DIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protection
guaranteed
Finger protection
guaranteed
Result of surge voltage test
Test passed
Result of power-frequency withstand voltage test
Test passed
Power frequency withstand voltage setpoint
1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)
Test passed
Result of flexion and pull-out test
Test passed
Bending test rotation speed
10
Bending test turns
135
Bending test conductor cross section/weight
0.2 mm² / 0.2 kg
Bending test conductor cross section/weight
6 mm² / 1.4 kg
Tensile test result
Test passed
Result of tight fit on support
Test passed
Tight fit on carrier
NS 35
Setpoint
5
Result of voltage-drop test
Test passed
Result of temperature-rise test
Test passed
Requirement temperature-rise test
Increase in temperature ≤ 45 K
Short circuit stability result
Test passed
Conductor cross section short circuit testing
6
Short-time current
0.72 kA
Result of thermal test
Test passed
Proof of thermal characteristics (needle flame) effective duration
30
Result of aging test
Test passed
Ageing test for screwless modular terminal block temperature cycles
192
Relative insulation material temperature index (Elec., UL 746 B)
130
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
130
Static insulating material application in cold
-60 °C
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Calorimetric heat release NFPA 130 (ASTM E 1354)
28
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Dimensions
Width
8.2 mm
End cover width
2.2 mm
Length
55
Height NS 35/7,5
47.5 mm
Height NS 35/15
55
Connection data
Connection method
Screw connection
Screw thread
M4
Stripping length
10
Tightening torque, min
1.5 Nm
Tightening torque max
1.8 Nm
Connection in acc. with standard
IEC 60947-7-1
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
10
Conductor cross section AWG min.
24
Conductor cross section AWG max.
8
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
10
Min. AWG conductor cross section, flexible
24
Max. AWG conductor cross section, flexible
8
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
6
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.
6
2 conductors with same cross section, solid min.
0.2 mm²
2 conductors with same cross section, solid max.
2.5 mm²
2 conductors with same cross section, stranded min.
0.2 mm²
2 conductors with same cross section, stranded max.
2.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
0.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
4
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
0.25 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
1.5 mm²
Ambient conditions
Operating temperature
-60 °C ... 105 °C (max. short-term operating temperature 130°C)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50 years
EAC RU C-DE.BL08.B.00534