Product Description:
Mini feed-through terminal block, nom. voltage: 500 V, nominal current: 17.5 A, connection method: Screw connection, number of connections: 2, cross section: 0.2 mm² - 2.5 mm², AWG: 24 - 14, width: 5 mm, color: blue, mounting type: NS 15

GTIN
: 04017918020200
Series
: MBK BU
Type
: Mini-aansluitklem
Key Features
- Mini feed-through terminal block
- nom. voltage: 500 V
- nominal current: 17.5 A
- connection method: Screw connection
- number of connections: 2
- cross section: 0.2 mm² - 2.5 mm²
- AWG: 24 - 14
- width: 5 mm
- color: blue
- mounting type: NS 15
Advantages
• MBK ... mini strip terminal blocks and their variants represent the original, typical shape of the MBK ... range
• Clear arrangement thanks to marking of all terminal points
• Space saving thanks to compact design and mounting option on a 15 mm DIN rail
• Easy potential distribution thanks to standardized plug-in bridges
Training Data Goes here
General
Number of levels
1
Number of connections
2
Potentials
1
Nominal cross section
1.5 mm²
Color
blue
Insulating material
PA
Flammability rating according to UL 94
V2
Rated surge voltage
6
Degree of pollution
3
Overvoltage category
III
Insulating material group
I
Maximum power dissipation for nominal condition
0.56 W
Maximum load current
24 A (with a 2.5 mm² conductor cross section)
Nominal current IN
17.5 A
Nominal voltage UN
500
Open side panel
No
Shock protection test specification
IEC 60529:2001-02
Back of the hand protection
guaranteed
Finger protection
guaranteed
Result of surge voltage test
Test passed
Result of power-frequency withstand voltage test
Test passed
Power frequency withstand voltage setpoint
1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)
Test passed
Result of flexion and pull-out test
Test passed
Bending test rotation speed
10
Bending test turns
135
Bending test conductor cross section/weight
0.2 mm² / 0.2 kg
Bending test conductor cross section/weight
1.5 mm² / 0.4 kg
Tensile test result
Test passed
Result of tight fit on support
Test passed
Tight fit on carrier
NS 15
Setpoint
1
Result of voltage-drop test
Test passed
Result of temperature-rise test
Test passed
Requirement temperature-rise test
Increase in temperature ≤ 45 K
Short circuit stability result
Test passed
Conductor cross section short circuit testing
1.5 mm²
Short-time current
0.18 kA
Conductor cross section short circuit testing
2.5 mm²
Short-time current
0.3 kA
Result of thermal test
Test passed
Proof of thermal characteristics (needle flame) effective duration
30
Relative insulation material temperature index (Elec., UL 746 B)
125
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
125
Dimensions
Width
5
Length
22
Height NS 15
23
Connection data
Connection
1
Connection method
Screw connection
Screw thread
M2,6
Stripping length
8
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Connection in acc. with standard
IEC 60947-7-1
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Min. AWG conductor cross section, flexible
24
Max. AWG conductor cross section, flexible
16
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
1.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.
1
Cross section with insertion bridge, solid max.
1.5 mm²
Cross section with insertion bridge, stranded max.
1.5 mm²
2 conductors with same cross section, solid min.
0.2 mm²
2 conductors with same cross section, solid max.
0.75 mm²
2 conductors with same cross section, stranded min.
0.2 mm²
2 conductors with same cross section, stranded max.
1
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
0.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
0.75 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
0.25 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
0.5 mm²
Internal cylindrical gage
A1
Ambient conditions
Operating temperature
-60 °C ... 105 °C (max. short-term operating temperature 125°C)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50 years
EAC RU C-DE.BL08.B.00534