Product Description:
Installation ground terminal block, Push-in connection, cross section: 0.2 mm² - 6 mm², AWG: 24 - 10, width: 6.2 mm, color: gray, mounting type: NS 35/7,5, NS 35/15

GTIN
: 04046356817790
Series
: PTI 4-PE/L/N
Type
: Installatie-aardklem
Key Features
- Instal.ation ground terminal block
- Push-in connection
- cross section: 0.2 mm² - 6 mm²
- AWG: 24 - 10
- width: 6.2 mm
- color: gray
- mounting type: NS 35/7
- NS 35/15
Advantages
• Compatible with all Phoenix Contact installation terminal blocks
• Each terminal point can be clearly labeled and easily recognized in every terminal block mounting position
• As well as the testing facility in the function shaft, each terminal point has a test contact
• Compact design tailored to distribution boards
• Double function shafts on all levels
• The new Push-in connection technology enables easy, direct insertion of solid and stranded conductors with ferrules with a cross section of 0.34 mm² or higher
Training Data Goes here
General
Number of levels
3
Number of connections
5
Potentials
2
Nominal cross section
4
Color
gray
Insulating material
PA
Flammability rating according to UL 94
V0
Rated surge voltage
6
Degree of pollution
3
Overvoltage category
III
Insulating material group
I
Maximum power dissipation for nominal condition
1.02 W (the value is multiplied when connecting multiple levels)
Maximum load current
32 A (with 6 mm² conductor cross section)
Nominal current IN
28 A (with 4 mm² conductor cross section)
Nominal voltage UN
400
Open side panel
Yes
Shock protection test specification
DIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protection
guaranteed
Finger protection
guaranteed
Result of surge voltage test
Test passed
Result of power-frequency withstand voltage test
Test passed
Power frequency withstand voltage setpoint
1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)
Test passed
Result of flexion and pull-out test
Test passed
Bending test rotation speed
10
Bending test turns
135
Bending test conductor cross section/weight
0.2 mm² / 0.2 kg
Bending test conductor cross section/weight
4 mm² / 0.9 kg
Tensile test result
Test passed
Result of voltage-drop test
Test passed
Result of temperature-rise test
Test passed
Requirement temperature-rise test
Increase in temperature ≤ 45 K
Short circuit stability result
Test passed
Conductor cross section short circuit testing
4
Short-time current
0.48 kA
Conductor cross section short circuit testing
6
Short-time current
0.72 kA
Result of thermal test
Test passed
Proof of thermal characteristics (needle flame) effective duration
30
Result of aging test
Test passed
Ageing test for screwless modular terminal block temperature cycles
192
Oscillation, broadband noise test result
Test passed
Test specification, oscillation, broadband noise
DIN EN 50155 (VDE 0115-200):2008-03
Test spectrum
Service life test category 2, bogie-mounted
Test frequency
f1 = 5 Hz to f2 = 250 Hz
ASD level
6.12 (m/s2)2/Hz
Acceleration
3.12 g
Test duration per axis
5
Test directions
X-, Y- and Z-axis
Shock test result
Test passed
Test specification, shock test
DIN EN 50155 (VDE 0115-200):2008-03
Shock form
Half-sine
Acceleration
30g
Shock duration
18
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)
130
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
130
Static insulating material application in cold
-60 °C
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Calorimetric heat release NFPA 130 (ASTM E 1354)
28
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Dimensions
Width
6.2 mm
End cover width
2.2 mm
Length
114
Height NS 35/7,5
50.5 mm
Height NS 35/15
58
Connection data
Connection
1st, 2nd and 3rd level
Connection method
Push-in connection
Stripping length
10 mm ... 12 mm
Connection in acc. with standard
IEC 60947-7-1
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
6
Conductor cross section AWG min.
24
Conductor cross section AWG max.
10
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
6
Min. AWG conductor cross section, flexible
24
Max. AWG conductor cross section, flexible
10
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
4
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.
4
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
0.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
1
Connection cross sections directly pluggable
0.5 mm² 6 mm²
Conductor cross section solid min.
0.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.5 mm²
Internal cylindrical gage
A4
Value
0.5 mm²
Value
4
Ambient conditions
Operating temperature
-60 °C ... 105 °C (max. short-term operating temperature 130°C)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Environmental Product Compliance
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
China RoHS
No hazardous substances above threshold values