Product Description:
High-current terminal block, nom. voltage: 1000 V, nominal current: 192 A, connection method: Screw connection, number of connections: 2, number of positions: 1, cross section: 16 mm² - 95 mm², AWG: 4 - 3/0, width: 20.3 mm, height: 80 mm, color: gray, mounting type: direct screw connection

GTIN
: 04046356607247
Series
: UKH 70-F
Type
: Klem voor hoge stromen
Key Features
- High-current terminal block
- nom. voltage: 1000 V
- nominal current: 192 A
- connection method: Screw connection
- number of connections: 2
- number of positions: 1
- cross section: 16 mm² - 95 mm²
- AWG: 4 - 3/0
- width: 20.3 mm
- height: 80 mm
- color: gray
- mounting type: direct screw connection
Advantages
• Reliable cable connection is ensured by three-point centering of the conductor in the prismatic sleeve base
• Low contact resistance of the contact surface due to ribbing
• Tested for railway applications
• Screw locking by means of spring-loaded elements in the clamping part
Training Data Goes here
General
Number of positions
1
Number of levels
1
Number of connections
2
Potentials
1
Nominal cross section
70
Color
gray
Insulating material
PA
Flammability rating according to UL 94
V0
Area of application
Railway industry
Area of application
Machine building
Area of application
Plant engineering
Rated surge voltage
8
Degree of pollution
3
Overvoltage category
III
Insulating material group
I
Maximum power dissipation for nominal condition
6.27 W
Maximum load current
192 A (in case of a 70 mm² conductor cross section, the maximum load current must not be exceeded by the total current of all connected conductors.)
Nominal current IN
192
Nominal voltage UN
1000
Open side panel
No
Shock protection test specification
DIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protection
guaranteed
Finger protection
guaranteed
Result of surge voltage test
Test passed
Result of power-frequency withstand voltage test
Test passed
Power frequency withstand voltage setpoint
2.2 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)
Test passed
Result of flexion and pull-out test
Test passed
Bending test conductor cross section/weight
25 mm² / 4.5 kg
Bending test conductor cross section/weight
70 mm²/10.4 kg
Tensile test result
Test passed
Result of tight fit on support
Test passed
Setpoint
10
Result of voltage-drop test
Test passed
Result of temperature-rise test
Test passed
Short circuit stability result
Test passed
Conductor cross section short circuit testing
70
Short-time current
8.4 kA
Result of thermal test
Test passed
Proof of thermal characteristics (needle flame) effective duration
30
Oscillation, broadband noise test result
Test passed
Test specification, oscillation, broadband noise
DIN EN 50155 (VDE 0115-200):2008-03
Test spectrum
Service life test category 1, class B, body mounted
Test frequency
f1 = 5 Hz to f2 = 150 Hz
ASD level
1.857 (m/s2)2/Hz
Acceleration
0,8 g
Test duration per axis
5
Test directions
X-, Y- and Z-axis
Shock test result
Test passed
Test specification, shock test
DIN EN 50155 (VDE 0115-200):2008-03
Shock form
Half-sine
Acceleration
5g
Shock duration
30
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)
130
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
130
Static insulating material application in cold
-60 °C
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Calorimetric heat release NFPA 130 (ASTM E 1354)
28
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Dimensions
Width
20.3 mm
Length
103.4 mm
Height
80
Connection data
Connection method
Screw connection
Screw thread
M8
Stripping length
24
Tightening torque, min
8
Tightening torque max
10
Connection in acc. with standard
IEC 60947-7-1
Note
Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area.
Conductor cross section solid min.
16
Conductor cross section solid max.
95
Conductor cross section AWG min.
4
Conductor cross section AWG max.
3/0
Conductor cross section flexible min.
25
Conductor cross section flexible max.
70
Min. AWG conductor cross section, flexible
3
Max. AWG conductor cross section, flexible
2/0
Conductor cross section flexible, with ferrule without plastic sleeve min.
16
Conductor cross section flexible, with ferrule without plastic sleeve max.
70
Conductor cross section flexible, with ferrule with plastic sleeve min.
16
Conductor cross section flexible, with ferrule with plastic sleeve max.
70
2 conductors with same cross section, solid min.
16
2 conductors with same cross section, solid max.
25
2 conductors with same cross section, stranded min.
16
2 conductors with same cross section, stranded max.
25
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
16
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
25
Internal cylindrical gage
A11
Ambient conditions
Operating temperature
-60 °C ... 105 °C (max. short-term operating temperature 130°C)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Environmental Product Compliance
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
China RoHS
No hazardous substances above threshold values