Product Description:
High-current terminal block, nom. voltage: 1500 V, nominal current: 309 A, connection method: Screw connection, number of connections: 2, cross section: 35 mm² - 150 mm², AWG: 2 - 300 kcmil, width: 31 mm, height: 107.3 mm, color: gray, mounting type: NS 35/15, NS 32

GTIN
: 04055626132976
Series
: UKH 150 1500V
Type
: Klem voor hoge stromen
Key Features
- High-current terminal block
- nom. voltage: 1500 V
- nominal current: 309 A
- connection method: Screw connection
- number of connections: 2
- cross section: 35 mm² - 150 mm²
- AWG: 2 - 300 kcmil
- width: 31 mm
- height: 107.3 mm
- color: gray
- mounting type: NS 35/15
- NS 32
Advantages
• Reliable cable connection is ensured by three-point centering of the conductor in the prismatic sleeve base
• Screw locking by means of spring-loaded elements in the clamping part
• Low contact resistance of the contact surface due to ribbing
Training Data Goes here
General
Number of levels
1
Number of connections
2
Potentials
1
Nominal cross section
150
Color
gray
Insulating material
PA
Flammability rating according to UL 94
V0
Rated surge voltage
8
Degree of pollution
3
Overvoltage category
III
Insulating material group
I
Maximum power dissipation for nominal condition
9.55 W
Maximum load current
309 A (with 150 mm² conductor cross section)
Nominal current IN
309
Nominal voltage UN
1500
Open side panel
No
Relative insulation material temperature index (Elec., UL 746 B)
130
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
130
Static insulating material application in cold
-60 °C
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Calorimetric heat release NFPA 130 (ASTM E 1354)
28
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Dimensions
Width
31
Length
100
Height
107.3 mm
Height NS 35/15
118.5 mm
Height NS 32
116
Connection data
Note
Screws with hexagonal socket
Connection method
Screw connection
Screw thread
M10
Stripping length
40
Tightening torque, min
25
Tightening torque max
30
Connection in acc. with standard
IEC 60947-7-1
Note
Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area.
Conductor cross section solid min.
35
Conductor cross section solid max.
150
Conductor cross section AWG min.
2
Conductor cross section AWG max.
300
Conductor cross section flexible min.
50
Conductor cross section flexible max.
150
Min. AWG conductor cross section, flexible
1/0
Max. AWG conductor cross section, flexible
300
Conductor cross section flexible, with ferrule without plastic sleeve min.
50
Conductor cross section flexible, with ferrule without plastic sleeve max.
150
Conductor cross section flexible, with ferrule with plastic sleeve min.
50
Conductor cross section flexible, with ferrule with plastic sleeve max.
150
Cross section with insertion bridge, solid max.
150
Cross section with insertion bridge, stranded max.
120
2 conductors with same cross section, solid min.
25
2 conductors with same cross section, solid max.
50
2 conductors with same cross section, stranded min.
35
2 conductors with same cross section, stranded max.
50
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
25
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
50
Internal cylindrical gage
B14
Ambient conditions
Operating temperature
-60 °C ... 105 °C (max. short-term operating temperature 125°C)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Environmental Product Compliance
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
China RoHS
No hazardous substances above threshold values
EAC RU C-DE.AI30.B.01102
EAC RU C-DE.BL08.B.00534