Product Description:
High-current terminal block, nom. voltage: 1000 V AC / 1500 V DC, nominal current: 150 A, connection method: Power-Turn connection, number of connections: 2, number of positions: 1, cross section: 10 mm² - 70 mm², AWG: 8 - 2/0, width: 20 mm, height: 96 mm, color: gray, mounting type: direct screw connection

GTIN
: 04046356998055
Series
: PTPOWER 50-F
Type
: Klem voor hoge stromen
Key Features
- High-current terminal block
- nom. voltage: 1000 V AC / 1500 V DC
- nominal current: 150 A
- connection method: Power-Turn connection
- number of connections: 2
- number of positions: 1
- cross section: 10 mm² - 70 mm²
- AWG: 8 - 2/0
- width: 20 mm
- height: 96 mm
- color: gray
- mounting type: direct screw connection
Advantages
• Quick and easy connection is now also possible for large conductors with the high-current terminal block
• The compact design enables wiring in a confined space
• In addition to using the existing test connection, pick-off terminal blocks can be connected, each of which can also accommodate two test cables
• The Push-in connection terminal blocks are characterized by the system features of the CLIPLINE complete system and by easy and tool-free wiring of conductors with ferrules or solid conductors
Training Data Goes here
General
Number of positions
1
Number of levels
1
Number of connections
2
Potentials
1
Nominal cross section
50
Color
gray
Insulating material
PA
Flammability rating according to UL 94
V0
Rated surge voltage
8
Degree of pollution
3
Overvoltage category
III
Insulating material group
I
Maximum power dissipation for nominal condition
4.73 W
Maximum load current
150 A (with 50 mm² conductor cross section)
Nominal current IN
150
Nominal voltage UN
1000
Nominal voltage UN
1500
Open side panel
No
Shock protection test specification
DIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protection
guaranteed
Finger protection
guaranteed
Result of surge voltage test
Test passed
Result of power-frequency withstand voltage test
Test passed
Result of the test for mechanical stability of terminal points (5 x conductor connection)
Test passed
Result of flexion and pull-out test
Test passed
Bending test rotation speed
10
Bending test turns
135
Bending test conductor cross section/weight
10 mm² / 2 kg
Bending test conductor cross section/weight
50 mm² / 9.5 kg
Tensile test result
Test passed
Result of tight fit on support
Test passed
Setpoint
10
Result of voltage-drop test
Test passed
Result of temperature-rise test
Test passed
Requirement temperature-rise test
Increase in temperature ≤ 45 K
Short circuit stability result
Test passed
Conductor cross section short circuit testing
50
Short-time current
6
Result of thermal test
Test passed
Proof of thermal characteristics (needle flame) effective duration
30
Result of aging test
Test passed
Ageing test for screwless modular terminal block temperature cycles
192
Oscillation, broadband noise test result
Test passed
Test specification, oscillation, broadband noise
DIN EN 50155 (VDE 0115-200):2018-05
Test spectrum
Service life test category 2, bogie-mounted
Test frequency
f1 = 5 Hz to f2 = 250 Hz
ASD level
6.12 (m/s2)2/Hz
Acceleration
3.12 g
Test duration per axis
5
Test directions
X-, Y- and Z-axis
Shock test result
Test passed
Test specification, shock test
DIN EN 50155 (VDE 0115-200):2018-05
Shock form
Half-sine
Acceleration
30g
Shock duration
18
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)
130
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
125
Static insulating material application in cold
-60 °C
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Calorimetric heat release NFPA 130 (ASTM E 1354)
27,5 MJ/kg
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Dimensions
Width
20
Length
101
Height
96
Hole diameter
6.5 mm
Drill hole spacing
123.4 mm
Pitch
20
Connection data
Connection
1
Connection method
Power-Turn connection
Stripping length
30 mm ... 32 mm
Connection in acc. with standard
IEC 60947-7-1
Conductor cross section solid min.
10
Conductor cross section solid max.
70
Conductor cross section AWG min.
8
Conductor cross section AWG max.
2/0
Conductor cross section flexible min.
10
Conductor cross section flexible max.
70
Min. AWG conductor cross section, flexible
8
Max. AWG conductor cross section, flexible
2/0
Conductor cross section flexible, with ferrule without plastic sleeve min.
10
Conductor cross section flexible, with ferrule without plastic sleeve max.
50
Conductor cross section flexible, with ferrule with plastic sleeve min.
10
Conductor cross section flexible, with ferrule with plastic sleeve max.
50
Cross section with insertion bridge solid min.
10
Cross section with insertion bridge, solid max.
50
Cross section with insertion bridge stranded min.
10
Cross section with insertion bridge, stranded max.
50
Cross section with insertion bridge stranded, with ferrule without plastic sleeve min.
10
Cross section with insertion bridge stranded, with ferrule without plastic sleeve max.
50
Cross section with insertion bridge stranded, with ferrule with plastic sleeve max.
50
Connection cross sections directly pluggable
10 mm² 70 mm² 8 2/0
Internal cylindrical gage
A10
Ambient conditions
Operating temperature
-60 °C ... 105 °C (max. short-term operating temperature 130°C)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Environmental Product Compliance
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
China RoHS
No hazardous substances above threshold values