Product Description:
Universal terminal block with bolt connection, bore hole on one side for M10 and on one side for M16, cross section: 70 - 240 mm², width: 53 mm, color: gray

GTIN
: 04046356578714
Series
: UHV240-AS 16/AS 10
Type
: Verbindingselementen voor hoge stro
Key Features
- Universal terminal block with bolt connection
- bore hole on one side for M10 and on one side for M16
- cross section: 70 - 240 mm²
- width: 53 mm
- color: gray
Advantages
• The UHV ... high-current connectors are available in several versions
• Versions are available with a cable lug or direct connection and there is a mixed version of both connection methods
• The comprehensive range of accessories, such as the connection rail for cross connection, ensures safe and user-friendly wiring of conductors up to 240 mm²
Training Data Goes here
General
Number of levels
1
Number of connections
2
Potentials
1
Color
gray
Insulating material
PA-F
Flammability rating according to UL 94
HB
Rated surge voltage
8
Degree of pollution
3
Overvoltage category
III
Insulating material group
II
Maximum load current
415 A (with 240 mm² conductor cross section)
Nominal current IN
415
Nominal voltage UN
1000
Open side panel
No
Dimensions
Width
53
Length
125
Height NS 35/15
58
Connection data
Connection method
Bolt connection
Stripping length
34
Tightening torque, min
25
Tightening torque max
30
Connection in acc. with standard
IEC 60947-7-1
Conductor cross section solid min.
70
Conductor cross section solid max.
240
Conductor cross section flexible min.
70
Conductor cross section flexible max.
240
Min. AWG conductor cross section, flexible
2/0
Max. AWG conductor cross section, flexible
500
Conductor cross section flexible, with ferrule without plastic sleeve min.
70
Conductor cross section flexible, with ferrule without plastic sleeve max.
180
Conductor cross section flexible, with ferrule with plastic sleeve min.
70
Conductor cross section flexible, with ferrule with plastic sleeve max.
185
2 conductors with same cross section, solid min.
35
2 conductors with same cross section, solid max.
95
2 conductors with same cross section, stranded min.
50
2 conductors with same cross section, stranded max.
95
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
35
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
50
Cable lug connection according to standard
DIN 46234:1980-03
Min. cross section for cable lug connection
25
Max. cross section for cable lug connection
240
Hole diameter, min.
17
Bolt diameter
16
Screw thread
M16
Tightening torque, min
30
Tightening torque max
35
Cable lug connection according to standard
DIN 46235:1983-07
Min. cross section for cable lug connection
50
Max. cross section for cable lug connection
185
Cable lug connection according to standard
DIN 46237:1970-07
Hole diameter, min.
11
Bolt diameter
10
Screw thread
M10
Power rail
40 mm x 5 mm
Ambient conditions
Operating temperature
-60 °C ... 85 °C
Ambient temperature (storage/transport)
-25 °C ... 55 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Standards and Regulations
Connection in acc. with standard
UL
Environmental Product Compliance
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
China RoHS
No hazardous substances above threshold values