Product Description:
Ground modular terminal block, nom. voltage: 500 V, nominal current: 20 A, connection method: Screw connection, cross section: 0.14 mm² - 6 mm², AWG: 26 - 10, length: 70.8 mm, width: 6.2 mm, color: gray, mounting: NS 35/7,5, NS 35/15

GTIN
: 04046356480239
Series
: UT 4 PE/MT
Type
: Aardklem
Key Features
- Ground mo.ular terminal block
- nom. voltage: 500 V
- nominal current: 20 A
- connection method: Screw connection
- cross section: 0.14 mm² - 6 mm²
- AWG: 26 - 10
- length: 70.8 mm
- width: 6.2 mm
- color: gray
- mounting: NS 35/7
- NS 35/15
Training Data Goes here
General
Number of levels
1
Number of connections
2
Nominal cross section
4
Color
gray
Insulating material
PA
Flammability rating according to UL 94
V0
Rated surge voltage
8
Degree of pollution
3
Overvoltage category
III
Insulating material group
I
Maximum power dissipation for nominal condition
1.02 W
Maximum load current
20 A (with 6 mm² conductor cross section)
Nominal current IN
20
Nominal voltage UN
500
Open side panel
No
Result of surge voltage test
Test passed
Result of power-frequency withstand voltage test
Test passed
Power frequency withstand voltage setpoint
1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)
Test passed
Result of flexion and pull-out test
Test passed
Bending test rotation speed
10
Bending test turns
135
Bending test conductor cross section/weight
0.2 mm² / 0.2 kg
Bending test conductor cross section/weight
4 mm² / 0.9 kg
Tensile test result
Test passed
Result of tight fit on support
Test passed
Tight fit on carrier
NS 35
Setpoint
1
Result of voltage-drop test
Test passed
Result of temperature-rise test
Test passed
Requirement temperature-rise test
Increase in temperature ≤ 45 K
Short circuit stability result
Test passed
Conductor cross section short circuit testing
2.5 mm²
Short-time current
0.3 kA
Result of thermal test
Test passed
Proof of thermal characteristics (needle flame) effective duration
30
Relative insulation material temperature index (Elec., UL 746 B)
130
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
130
Static insulating material application in cold
-60 °C
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Calorimetric heat release NFPA 130 (ASTM E 1354)
28
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Dimensions
Width
6.2 mm
Length
70.8 mm
Height NS 35/7,5
49.1 mm
Height NS 35/15
56.6 mm
Connection data
Note
Please observe the current carrying capacity of the DIN rails.
Connection method
Screw connection
Screw thread
M3
Stripping length
9
Tightening torque, min
0.6 Nm
Tightening torque max
0.8 Nm
Connection in acc. with standard
IEC 60947-7-1/IEC 60947-7-2
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
6
Conductor cross section AWG min.
26
Conductor cross section AWG max.
10
Conductor cross section flexible min.
0.14 mm²
Conductor cross section flexible max.
6
Min. AWG conductor cross section, flexible
26
Max. AWG conductor cross section, flexible
10
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
4
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.
4
Internal cylindrical gage
A4
Ambient conditions
Operating temperature
-60 °C ... 105 °C (max. short-term operating temperature 125°C)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Standards and Regulations
Connection in acc. with standard
CSA
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50 years