Ground modular terminal block, connection method: Screw connection, number of connections: 2, number of positions: 1, cross section: 0.2 mm² - 4 mm², AWG: 24 - 12, width: 6.2 mm, color: green-yellow, mounting type: NS 35/7,5, NS 35/15, NS 32
GTIN
: 04017918002121
Series
: USLKG 4
Type
: Aardklem
Key Features
- Ground m.dular terminal block
- connection method: Screw connection
- number of connections: 2
- number of positions: 1
- cross section: 0.2 mm² - 4 mm²
- AWG: 24 - 12
- width: 6.2 mm
- color: green-yellow
- mounting type: NS 35/7
- NS 35/15
- NS 32
Training Data Goes here
General
Note
When aligning with a feed-through terminal block with the same shape, an end cover must be interposed with insulation voltages of > 690 V
Number of positions
1
Number of levels
1
Number of connections
2
Color
green-yellow
Insulating material
PA
Flammability rating according to UL 94
V0
Rated surge voltage
8
Degree of pollution
3
Overvoltage category
III
Insulating material group
I
Open side panel
No
Relative insulation material temperature index (Elec., UL 746 B)
130
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
130
Static insulating material application in cold
-60 °C
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Calorimetric heat release NFPA 130 (ASTM E 1354)
28
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Dimensions
Width
6.2 mm
Length
42.5 mm
Height NS 35/7,5
47
Height NS 35/15
54.5 mm
Height NS 32
52
Connection data
Note
Please observe the current carrying capacity of the DIN rails.
Connection method
Screw connection
Screw thread
M3
Stripping length
9
Tightening torque, min
0.6 Nm
Tightening torque max
0.8 Nm
Connection in acc. with standard
IEC 60947-7-2
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4
Min. AWG conductor cross section, flexible
24
Max. AWG conductor cross section, flexible
12
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
2.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.
1.5 mm²
2 conductors with same cross section, solid min.
0.2 mm²
2 conductors with same cross section, solid max.
1.5 mm²
2 conductors with same cross section, stranded min.
0.2 mm²
2 conductors with same cross section, stranded max.
1
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
0.25 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
1.5 mm²
Ambient conditions
Operating temperature
-60 °C ... 105 °C (max. short-term operating temperature 130°C)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Standards and Regulations
Connection in acc. with standard
CSA
Environmental Product Compliance
REACh SVHC
4-Nonylphenol, ethoxylated
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
China RoHS
No hazardous substances above threshold values