Phoenix Contact Fuse modular terminal block - PT 4-HESILED 24 (5X20) BU/BU - 3211905
Product Description:
Fuse modular terminal block, fuse type: Glass / ceramics / ..., connection method: Push-in connection, cross section: 0.2 mm²- 6 mm², AWG: 24 - 10, nominal current: 6.3 A, nom. voltage: 24 V, width: 6.2 mm, fuse type: G / 5 x 20, mounting type: NS 35/7,5, NS 35/15, color: blue

GTIN
: 04055626302829
Series
: PT 4-HESILED 24 (5X20) BU/BU
Type
: Zekeringsaansluitklem
Key Features
- Fuse modu.ar terminal block
- fuse type: Glass / ceramics / ...
- connection method: Push-in connection
- cross section: 0.2 mm²- 6 mm²
- AWG: 24 - 10
- nominal current: 6.3 A
- nom. voltage: 24 V
- width: 6.2 mm
- fuse type: G / 5 x 20
- mounting type: NS 35/7
- NS 35/15
- color: blue
Advantages
• In addition to the testing facility in the double function shaft, all terminal blocks provide an additional test connection
• The compact design and front connection enable wiring in a confined space
• The Push-in connection terminal blocks are characterized by the system features of the CLIPLINE complete system and by easy and tool-free wiring of conductors with ferrules or solid conductors
• Tested for railway applications
Training Data Goes here
General
Note
The current is determined by the fuse used, the voltage by the selected LED.If the fuse is faulty, the downstream circuit will not be disconnected.
Number of levels
1
Number of connections
2
Nominal cross section
4
Color
blue
Insulating material
PA
Flammability rating according to UL 94
V0
Area of application
Railway industry
Area of application
Machine building
Area of application
Plant engineering
Maximum power dissipation for nominal condition
1.6 W
Rated surge voltage
4
Degree of pollution
3
Overvoltage category
III
Insulating material group
I
Maximum power dissipation
max. 1.6 W (with single arrangement of the fuse terminal block in the event of overload)
Maximum power dissipation
max. 1.6 W (With interconnected arrangement of several fuse terminal blocks in the event of overload)
Maximum power dissipation
max. 4 W (with single arrangement of the fuse terminal block in the event of a short-circuit)
Maximum power dissipation
max. 2.5 W (With interconnected arrangement of several fuse terminal blocks in the event of a short-circuit)
LED voltage range
12 V AC/DC ... 30 V AC/DC
LED current range
0.31 mA ... 0.95 mA
Connection in acc. with standard
IEC 60947-7-3
Maximum load current
6.3 A (with 6 mm² conductor cross section, rigid)
Nominal current IN
6.3 A
Nominal voltage UN
24
Fuse
G / 5 x 20
Fuse type
Glass / ceramics / ...
Open side panel
Yes
Relative insulation material temperature index (Elec., UL 746 B)
130
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
130
Static insulating material application in cold
-60 °C
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Calorimetric heat release NFPA 130 (ASTM E 1354)
28
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Dimensions
Width
6.2 mm
End cover width
2.2 mm
Length
56
Height
63.4 mm
Height NS 35/7,5
62.5 mm
Height NS 35/15
70
Ambient conditions
Operating temperature
-60 °C ... 105 °C (max. short-term operating temperature 130°C)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Connection data
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
6
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
6
Conductor cross section AWG min.
24
Conductor cross section AWG max.
10
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
4
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.
4
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
0.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
1
Connection method
Push-in connection
Stripping length
10 mm ... 12 mm
Internal cylindrical gage
A4
Environmental Product Compliance
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
China RoHS
No hazardous substances above threshold values