Product Description:
Feed-through terminal block, nom. voltage: 500 V, nominal current: 32 A, connection method: Screw/plug-in connection, number of connections: 3, number of positions: 1, cross section: 0.14 mm² - 6 mm², AWG: 26 - 10, width: 6.2 mm, color: gray, mounting type: NS 35/7,5, NS 35/15

GTIN
: 04046356090391
Series
: UT 4-TWIN/ 1P
Type
: Aansluitklem
Key Features
- Feed-throu.h terminal block
- nom. voltage: 500 V
- nominal current: 32 A
- connection method: Screw/plug-in connection
- number of connections: 3
- number of positions: 1
- cross section: 0.14 mm² - 6 mm²
- AWG: 26 - 10
- width: 6.2 mm
- color: gray
- mounting type: NS 35/7
- NS 35/15
Advantages
• Plugs with different conductor exit directions (lateral or upwards) enable practical, efficient wiring. This results in a high degree of flexibility, which is required in various areas of application.
• Screw flanges for securely latching plugs
Training Data Goes here
General
Number of positions
1
Number of levels
1
Number of connections
3
Potentials
1
Nominal cross section
4
Color
gray
Insulating material
PA
Flammability rating according to UL 94
V0
Rated surge voltage
6
Degree of pollution
3
Overvoltage category
III
Insulating material group
I
Maximum power dissipation for nominal condition
1.02 W
Maximum load current
32 A (In the case of a 6 mm² conductor cross section, the maximum load current must not be exceeded by the total current of all connected conductors)
Nominal current IN
32 A (observe derating)
Nominal voltage UN
500
Open side panel
Yes
Result of surge voltage test
Test passed
Result of tight fit on support
Test passed
Tight fit on carrier
NS 35
Setpoint
1
Short circuit stability result
Test passed
Conductor cross section short circuit testing
4
Short-time current
0.48 kA
Result of thermal test
Test passed
Proof of thermal characteristics (needle flame) effective duration
30
Oscillation, broadband noise test result
Test passed
Test specification, oscillation, broadband noise
DIN EN 50155 (VDE 0115-200):2008-03
Test spectrum
Service life test category 1, class B, body mounted
Test frequency
f1 = 5 Hz to f2 = 150 Hz
ASD level
0.02 g²/Hz
Acceleration
0,8 g
Test duration per axis
5
Test directions
X-, Y- and Z-axis
Shock test result
Test passed
Test specification, shock test
DIN EN 50155 (VDE 0115-200):2008-03
Shock form
Half-sine
Acceleration
5g
Shock duration
30
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)
130
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
130
Static insulating material application in cold
-60 °C
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Calorimetric heat release NFPA 130 (ASTM E 1354)
28
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Dimensions
Width
6.2 mm
End cover width
2.2 mm
Length
55.7 mm
Height NS 35/7,5
47.5 mm
Height NS 35/15
55
Connection data
Connection method
Screw/plug-in connection
Screw thread
M3
Stripping length
9
Tightening torque, min
0.6 Nm
Tightening torque max
0.8 Nm
Connection in acc. with standard
IEC 61984
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
6
Conductor cross section AWG min.
26
Conductor cross section AWG max.
10
Conductor cross section flexible min.
0.14 mm²
Conductor cross section flexible max.
6
Min. AWG conductor cross section, flexible
26
Max. AWG conductor cross section, flexible
10
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
4
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.
4
2 conductors with same cross section, solid min.
0.14 mm²
2 conductors with same cross section, solid max.
1.5 mm²
2 conductors with same cross section, stranded min.
0.14 mm²
2 conductors with same cross section, stranded max.
1.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
0.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
1
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
0.14 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
1.5 mm²
Internal cylindrical gage
A4
Ambient conditions
Operating temperature
-60 °C (maximum operating temperature see derating curve)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Standards and Regulations
Connection in acc. with standard
CSA
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50 years