Product Description:
1-level terminal block with double connection on one side, cross section: 0.2 - 4 mm², AWG: 24 - 12, width: 6.2 mm, color: Brown

GTIN
: 04046356075572
Series
: UK 5-TWIN BN
Type
: Aansluitklem
Key Features
- 1-level terminal block with double connection on one side
- cross section: 0.2 - 4 mm²
- AWG: 24 - 12
- width: 6.2 mm
- color: Brown
Training Data Goes here
General
Number of positions
1
Number of levels
2
Number of connections
3
Potentials
1
Nominal cross section
4
Color
brown
Insulating material
PA
Flammability rating according to UL 94
V2
Rated surge voltage
6
Degree of pollution
3
Overvoltage category
III
Insulating material group
I
Maximum power dissipation for nominal condition
1.02 W (the value is multiplied when connecting multiple levels)
Maximum load current
32 A (in case of a 4 mm² conductor cross section, the maximum load current must not be exceeded by the total current of all connected conductors.)
Nominal current IN
32 A (with 4 mm² conductor cross section)
Nominal voltage UN
500 V (With tightened clamping screws)
Open side panel
Yes
Shock protection test specification
DIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protection
guaranteed
Finger protection
guaranteed
Result of surge voltage test
Test passed
Surge voltage test setpoint
7.2 kV
Result of power-frequency withstand voltage test
Test passed
Power frequency withstand voltage setpoint
1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)
Test passed
Result of flexion and pull-out test
Test passed
Bending test rotation speed
10 (+/- 2) rpm
Bending test turns
135
Bending test conductor cross section/weight
0.2 mm² / 0.2 kg
Bending test conductor cross section/weight
1.5 mm² / 0.4 kg
Tensile test result
Test passed
Conductor cross section tensile test
0.2 mm²
Tractive force setpoint
10
Conductor cross section tensile test
1.2 mm²
Tractive force setpoint
40
Conductor cross section tensile test
4
Tractive force setpoint
60
Result of tight fit on support
Test passed
Tight fit on carrier
NS 32/NS 35
Setpoint
1
Result of voltage-drop test
Test passed
Requirements, voltage drop
U1 ≤ 3,2 mVU2 ≤ 1,5 x U1dT ≤ 45 K
Result of temperature-rise test
Test passed
Requirement temperature-rise test
Increase in temperature ≤ 45 K
Short circuit stability result
Test passed
Conductor cross section short circuit testing
4000000
Short-time current
0.00048 kA
Result of thermal test
Test passed
Proof of thermal characteristics (needle flame) effective duration
30
Ageing test for screwless modular terminal block temperature cycles
192
Test specification, oscillation, broadband noise
DIN EN 50155 (VDE 0115-200):2018-05
Test spectrum
Service life test category 2, bogie-mounted
Test frequency
f1 = 5 Hz to f2 = 250 Hz
ASD level
6.12 (m/s2)2/Hz
Acceleration
3.12 g
Test duration per axis
5
Test directions
X-, Y- and Z-axis
Shock form
Half-sine
Acceleration
30g
Shock duration
18
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)
130
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
130
Static insulating material application in cold
-60 °C
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Calorimetric heat release NFPA 130 (ASTM E 1354)
28
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Dimensions
Width
6.2 mm
End cover width
2
Length
50.5 mm
Height NS 35/7,5
47
Height NS 35/15
54.5 mm
Height NS 32
52
Connection data
Connection
1
Connection method
Screw connection
Screw thread
M3
Stripping length
8
Tightening torque, min
0.6 Nm
Tightening torque max
0.8 Nm
Connection in acc. with standard
IEC 60947-7-1
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4
Min. AWG conductor cross section, flexible
24
Max. AWG conductor cross section, flexible
12
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
4
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.
2.5 mm²
Cross section with insertion bridge, solid max.
4
Cross section with insertion bridge, stranded max.
4
2 conductors with same cross section, solid min.
0.2 mm²
2 conductors with same cross section, solid max.
1.5 mm²
2 conductors with same cross section, stranded min.
0.2 mm²
2 conductors with same cross section, stranded max.
1.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
0.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
1.5 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
0.25 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
1.5 mm²
Connection in acc. with standard
IEC/EN 60079-7
Internal cylindrical gage
A4
Ambient conditions
Operating temperature
-60 °C ... 105 °C (max. short-term operating temperature 125°C)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Standards and Regulations
Connection in acc. with standard
CSA
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years