Product Description:
Disconnect terminal block, With test socket screws for insertion of test plugs, nom. voltage: 500 V, nominal current: 20 A, connection method: Screw connection, cross section: 0.2 mm² - 10 mm², AWG: 24 - 8, length: 57.8 mm, width: 8.2 mm, color: gray, mounting: NS 35/7,5, NS 35/15

GTIN
: 04046356919203
Series
: UT 6-TG P/P-EX
Type
: Scheidingsklem
Key Features
- Disconnect.terminal block
- With test socket screws for insertion of test plugs
- nom. voltage: 500 V
- nominal current: 20 A
- connection method: Screw connection
- cross section: 0.2 mm² - 10 mm²
- AWG: 24 - 8
- length: 57.8 mm
- width: 8.2 mm
- color: gray
- mounting: NS 35/7
- NS 35/15
Advantages
• Double bridge shaft enables individual potential distribution and supply
• Compact design and high current carrying capacity of 20 A
• Suitable for process technology, thanks to Ex nA approval
Training Data Goes here
General
Note
Current and voltage are determined by the plug used.
Number of levels
1
Number of connections
2
Nominal cross section
6
Color
gray
Insulating material
PA
Flammability rating according to UL 94
V0
Area of application
Machine building
Area of application
Plant engineering
Rated surge voltage
6
Degree of pollution
3
Overvoltage category
III
Insulating material group
I
Connection in acc. with standard
IEC 60947-7-1
Nominal current IN
20
Maximum load current
20 A (with 10 mm² conductor cross section)
Nominal voltage UN
500
Open side panel
No
Maximum power dissipation for nominal condition
1.31 W
Relative insulation material temperature index (Elec., UL 746 B)
130
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
130
Static insulating material application in cold
-60 °C
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Calorimetric heat release NFPA 130 (ASTM E 1354)
28
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Dimensions
Width
8.2 mm
Length
57.8 mm
Height NS 35/7,5
47.5 mm
Height NS 35/15
55
Connection data
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
10
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
10
Conductor cross section AWG min.
24
Conductor cross section AWG max.
8
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
6
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.
6
2 conductors with same cross section, solid min.
0.2 mm²
2 conductors with same cross section, solid max.
2.5 mm²
2 conductors with same cross section, stranded min.
0.2 mm²
2 conductors with same cross section, stranded max.
2.5 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
0.25 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
1.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
0.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
4
Connection method
Screw connection
Stripping length
10
Internal cylindrical gage
A5
Screw thread
M4
Tightening torque, min
1.5 Nm
Tightening torque max
1.8 Nm
Ambient conditions
Operating temperature
-60 °C ... 105 °C (max. short-term operating temperature 125°C)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50 years