Product Description:
Disconnect terminal block, connection method: Screw connection, cross section: 0.5 mm² - 10 mm² , AWG: 20 - 10, width: 8.2 mm, mounting type: NS 35/7,5, NS 35/15, NS 32, color: red

GTIN
: 04046356519236
Series
: URTK/S-IB RD
Type
: Scheidingsklem
Key Features
- Disco.nect terminal block
- connection method: Screw connection
- cross section: 0.5 mm² - 10 mm²
- AWG: 20 - 10
- width: 8.2 mm
- mounting type: NS 35/7
- NS 35/15
- NS 32
- color: red
Advantages
• Easy and clear testing in current transformer secondary circuits can be performed using the test disconnect terminal blocks of the URTK/S range
• On both sides of the disconnect point, the terminal block has a test socket which can also be used to switch across to neighboring terminal blocks
Training Data Goes here
General
Number of levels
1
Number of connections
2
Potentials
1
Nominal cross section
6
Color
red
Insulating material
PA
Flammability rating according to UL 94
V0
Rated surge voltage
6
Degree of pollution
3
Overvoltage category
III
Insulating material group
I
Maximum power dissipation for nominal condition
1.31 W
Maximum load current
57 A (with 10 mm² conductor cross section)
Nominal current IN
41
Nominal voltage UN
400
Open side panel
Yes
Shock protection test specification
IEC 60529:2001-02
Back of the hand protection
guaranteed
Result of surge voltage test
Test passed
Result of power-frequency withstand voltage test
Test passed
Power frequency withstand voltage setpoint
1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)
Test passed
Result of flexion and pull-out test
Test passed
Bending test rotation speed
10
Bending test turns
135
Bending test conductor cross section/weight
0.5 mm² / 0.3 kg
Bending test conductor cross section/weight
6 mm² / 1.4 kg
Tensile test result
Test passed
Result of tight fit on support
Test passed
Tight fit on carrier
NS 32/NS 35
Setpoint
5
Result of voltage-drop test
Test passed
Result of temperature-rise test
Test passed
Requirement temperature-rise test
Increase in temperature ≤ 45 K
Short circuit stability result
Test passed
Conductor cross section short circuit testing
6
Short-time current
0.72 kA
Conductor cross section short circuit testing
10
Short-time current
1.2 kA
Result of thermal test
Test passed
Proof of thermal characteristics (needle flame) effective duration
30
Relative insulation material temperature index (Elec., UL 746 B)
130
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
130
Static insulating material application in cold
-60 °C
Dimensions
Width
8.2 mm
End cover width
2.2 mm
Length
72
Height NS 35/7,5
51.5 mm
Height NS 35/15
59
Height NS 32
56.5 mm
Connection data
Note
Terminal point
Connection
1
Connection method
Screw connection
Screw thread
M4
Stripping length
13
Tightening torque, min
1.2 Nm
Tightening torque max
1.5 Nm
Connection in acc. with standard
IEC 60947-7-1
Conductor cross section solid min.
0.5 mm²
Conductor cross section solid max.
10
Conductor cross section AWG min.
20
Conductor cross section AWG max.
8
Conductor cross section flexible min.
0.5 mm²
Conductor cross section flexible max.
6
Min. AWG conductor cross section, flexible
20
Max. AWG conductor cross section, flexible
10
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
6
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.
4
2 conductors with same cross section, solid min.
0.5 mm²
2 conductors with same cross section, solid max.
2.5 mm²
2 conductors with same cross section, stranded min.
0.5 mm²
2 conductors with same cross section, stranded max.
6
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
0.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
4
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
0.5 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
4
Internal cylindrical gage
A5
Ambient conditions
Operating temperature
-60 °C ... 85 °C
Ambient temperature (storage/transport)
-25 °C ... 55 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)
30 % ... 70 %
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Environmental Product Compliance
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
China RoHS
No hazardous substances above threshold values
EAC EAC-Zulassung
EAC RU C-DE.BL08.B.00534