Product Description:
MCR current measuring transducer, for measuring sinusoidal and non-sinusoidal alternating currents, input current 0...100 A, output voltage 0...(5) 10 V

GTIN
: 04046356043632
Series
: MCR-SL-S-100-U
Type
: Stroommeetwaardeomvormer
Key Features
- MCR current measuring transducer
- for measuring sinusoidal and non-sinusoidal alternating currents
- input current 0...100 A
- output voltage 0... 10 V
Advantages
• Can be retrofitted with open-up Rogowski coil
• Loop-powered
• 30 6000 Hz true r.m.s. value measurement
• Measuring range selection via slide switch
Training Data Goes here
Dimensions
Width
55
Height
85
Depth
70.5 mm
Primary round conductor (diameter)
18.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 60 °C
Degree of protection
IP20
Input data
Input
Current measuring input
Input current range
0 A ... 100 A (0 ... 50/75/100 A)
Operate threshold
1 % (of final value)
Setting range for min. input current
0 A ... 50 A
Setting range for max. input current
0 A ... 100 A
Overload capacity
Depending on laid conductor
Surge strength
Depending on through connected conductor
Frequency measuring range
30 Hz ... 6000 Hz
Output data
Output name
Voltage output
Voltage output signal
0 V ... 10 V
Voltage output signal
0 V ... 5 V
Max. output voltage
(0 V ... 10 V) 14 V, (0 V ... 5 V) 7 V
Load/output load voltage output
≥ 10 kΩ
Switching output
Output name
No switching output
Power supply
Nominal supply voltage
24
Max. current consumption
< 30 mA
Connection data
Connection method
Pluggable screw connection
Stripping length
8
Screw thread
M3
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Torque
0.5 Nm ... 0.6 Nm (4,4 ... 5,31 lbf-in.)
General
Maximum transmission error
< 1 % (of final value)
Maximum temperature coefficient
< 0.035 %/K
Step response (10-90%)
< 340 ms
Overvoltage category
III
Degree of pollution
2
Rated insulation voltage
300 V AC (to earth)
Test voltage input/output
5 kV (50 Hz, 1 min.)
Color
green
Housing material
Polyamide PA non-reinforced
Mounting position
any
Standards and Regulations
Conformance
CE-compliant
UL, USA/Canada
UL/C-UL listed UL 508
Conformance/approvals
Designation
CE
Identification
CE-compliant
Designation
UL, USA/Canada
Identification
UL/C-UL Listed UL 508
Identification
Class I, Div. 2, Groups A, B, C, D T4A
Identification
Class I, Zone 2, Group IIC T4A
Identification
Or Non-Hazardous Locations only
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 25;