Product Description:
MCR current measuring transducer, programmable and configurable, for measuring direct, alternating and distorted currents, with relay and transistor output, input current 0...10 to 0...50 A, unconfigured

GTIN
: 04017918169299
Series
: MCR-S-10-50-UI-SW-DCI-NC
Type
: Stroommeetwaardeomvormer
Key Features
- MCR current measuring transducer
- programmable and configurable
- for measuring direct
- alternating and distorted currents
- with relay and transistor output
- input current 0...10 to 0...50 A
- unconfigured
Advantages
• 3-way isolation
• True r.m.s. value measurement
• Device can be set via DIP switches or MCR/PI-CONF-WIN configuration software
Training Data Goes here
Dimensions
Width
22.5 mm
Height
99
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Maximum altitude
< 2000 m
Degree of protection
IP20
Noise immunity
EN 61000-6-2
Input data
Input
Current measuring input
Configurable/programmable
Yes, unconfigured
Input current range
0 A ... 55 A (AC/DC)
Operate threshold
0.8 % (of measuring range nominal value 50 A)
Setting range for min. input current
0 A ... 9.5 A
Setting range for max. input current
0 A ... 55 A
Impulse form
AC, DC or distorted currents
Overload capacity
Depending on through connected conductor
Surge strength
Depending on through connected conductor
Frequency measuring range
15 Hz ... 400 Hz
Connection method
Through connection, diameter 10.5 mm
Output data
Output name
Voltage output / current output
Voltage output signal
0 V ... 10 V
Voltage output signal
2 V ... 10 V
Voltage output signal
-10 V ... 10 V
Voltage output signal
0 V ... 5 V
Voltage output signal
1 V ... 5 V
Voltage output signal
-5 V ... 5 V
Voltage output signal
10 V ... 0 V
Voltage output signal
10 V ... 2 V
Voltage output signal
10 V ... -10 V
Voltage output signal
5 V ... 0 V
Voltage output signal
5 V ... 1 V
Voltage output signal
5 V ... -5 V
Current output signal
0 mA ... 20 mA
Current output signal
4 mA ... 20 mA
Current output signal
20 mA ... 0 mA
Current output signal
20 mA ... 4 mA
Load/output load voltage output
> 10 kΩ
Load/output load current output
< 500 Ω
Switching output
Output name
Relay output
Contact type
1 changeover contact
Contact material
AgSnO, hard gold-plated
Maximum switching voltage
30
Maximum switching voltage
36
Maximum switching voltage
250 V AC (when the gold layer is destroyed)
Limiting continuous current
50
Limiting continuous current
2 A (when the gold layer is destroyed)
Output name
Transistor output, pnp
Output voltage range
19 V ... 29 V (supply voltage - 1 V)
Continuous load current
80 mA (Not short-circuit proof)
Setting range of the threshold value
1 % ... 110 %
Setting range of the response delay
0.1 s ... 20 s
Status display
Yellow LED
Power supply
Supply voltage range
20 V DC ... 30 V DC
Max. current consumption
< 50 mA (without load)
Connection data
Connection method
Screw connection
Stripping length
8
Screw thread
M3
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
General
Maximum transmission error
< 0.5 % (of nominal range value under nominal conditions)
Temperature coefficient, typical
< 0.025 %/K
Step response (10-90%)
330 ms (with AC)
Step response (10-90%)
40 ms (with DC)
Status display
Green LED
Overvoltage category
III
Degree of pollution
2
Rated insulation voltage
300 V AC (to earth)
Test voltage input/output
4 kV (50 Hz, 1 min.)
Test voltage input/power supply
4 kV (50 Hz, 1 min.)
Test voltage output/power supply
500 V (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Color
green
Housing material
Polyamide PA non-reinforced
Mounting position
any
Standards and Regulations
Connection in acc. with standard
CUL
Low Voltage Directive
Conformance with Low Voltage Directive
Conformance
CE-compliant
UL, USA/Canada
Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X
UL, USA/Canada
Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only
Conformance/approvals
Designation
CE
Identification
CE-compliant
Designation
UL, USA/Canada
Identification
Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X
Identification
Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years