Connection terminal block, connection method: Screw connection, load current: 41 A, cross section: 0.5 mm² - 6 mm², width: 7 mm, color: blue
GTIN
: 04017918001919
Series
: AKG 4 BU
Type
: Aansluitklem
Key Features
- Connection terminal block
- connection method: Screw connection
- load current: 41 A
- cross section: 0.5 mm² - 6 mm²
- width: 7 mm
- color: blue
Training Data Goes here
General
Color
blue
Insulating material
PA
Nominal cross section
4
Flammability rating according to UL 94
V2
Maximum load current
41
Maximum power dissipation for nominal condition
1.31 W
Nominal current IN
41
Maximum load current
41 A (with 6 mm² conductor cross section)
Nominal voltage UN
300
Result of the test for mechanical stability of terminal points (5 x conductor connection)
Test passed
Result of flexion and pull-out test
Test passed
Bending test rotation speed
10
Bending test turns
135
Bending test conductor cross section/weight
0.5 mm² / 0.3 kg
Bending test conductor cross section/weight
4 mm² / 0.9 kg
Bending test conductor cross section/weight
6 mm² / 1.4 kg
Tensile test result
Test passed
Conductor cross section tensile test
0.5 mm²
Tractive force setpoint
30
Conductor cross section tensile test
4
Tractive force setpoint
60
Conductor cross section tensile test
6
Tractive force setpoint
80
Result of voltage-drop test
Test passed
Requirements, voltage drop
≤ 3.2 mV
Result of temperature-rise test
Test passed
Short circuit stability result
Test passed
Conductor cross section short circuit testing
4
Short-time current
0.48 kA
Relative insulation material temperature index (Elec., UL 746 B)
125
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
125
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
Dimensions
Length
23.4 mm
Width
7
Connection data
Conductor cross section solid min.
0.5 mm²
Conductor cross section solid max.
6
Conductor cross section flexible min.
0.5 mm²
Conductor cross section flexible max.
4
Conductor cross section AWG min.
20
Conductor cross section AWG max.
10
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
6
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.
6
2 conductors with same cross section, solid min.
0.5 mm²
2 conductors with same cross section, solid max.
2.5 mm²
2 conductors with same cross section, stranded min.
0.5 mm²
2 conductors with same cross section, stranded max.
2.5 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
0.5 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
2.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
0.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
2.5 mm²
Connection method
Screw connection
Stripping length
16
Screw thread
M4
Tightening torque, min
1.5 Nm
Tightening torque max
1.8 Nm
Standards and Regulations
Connection in acc. with standard
CUL
Environmental Product Compliance
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
China RoHS
No hazardous substances above threshold values