Product Description:
Surge protective device, three-channel with remote indicator contact for 120/240 V split-phase or 120/208 V Wye three-phase AC, 4-wire.

GTIN
: 04055626444994
Series
: VAL-US-120/65/3+0-FM
Type
: Overspanningsbeveiligingsmoduul Typ
Key Features
- Surge protective device
- three-channel with remote indicator contact for 120/240 V split-phase or 120/208 V Wye three-phase AC
- 4-wire.
Advantages
• UL open terminal listed SPD
• With floating remote indication contact
• Plugs can be checked with CHECKMASTER
• Secure hold of plugs in the event of high lightning current loads and strong vibrations thanks to new latching
• Mechanical coding of all slots
• Optical, mechanical status indication for the individual arresters
• Pluggable
• Thermal disconnect device for each individual plug
Training Data Goes here
Dimensions
Height
98.7 mm
Width
53.4 mm
Depth
77.5 mm
Horizontal pitch
3
Ambient conditions
Degree of protection
IP20 (only when all terminal points are used)
Ambient temperature (operation)
-40 °C ... 80 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % ... 95 %
Shock (operation)
30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
General
IEC test classification
I / II
IEC test classification
T1 / T2
EN type
T1 / T2
IEC power supply system
TN-C
Mode of protection
L-PEN
Mounting type
DIN rail: 35 mm
Color
jet black RAL 9005
Housing material
PA 6.6
Housing material
PBT
Degree of pollution
2
Flammability rating according to UL 94
V-0
Type
DIN rail module, two-section, divisible
Number of positions
3
Surge protection fault message
Optical, remote indicator contact
Protective circuit
Nominal voltage UN
120/208 V AC (TN-C)
Nominal frequency fN
50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-PEN)
175
Rated load current IL
80
Residual current IPE
≤ 0.8 mA
Nominal discharge current In (8/20) µs
20
Nominal discharge current In (8/20) µs (L-PEN)
12.5 kA
Total discharge current Itotal (10/350) µs
37.5 kA
Short-circuit current rating ISCCR
25
Voltage protection level Up
≤ 0.8 kV
Residual voltage Ures
≤ 0.8 kV (at In)
Residual voltage Ures
≤ 0.75 kV (at 10 kA)
Residual voltage Ures
≤ 0.65 kV (at 5 kA)
Residual voltage Ures
≤ 0.5 kV (at 3 kA)
TOV behavior at UT
208 V AC (5 s / withstand mode)
TOV behavior at UT
240 V AC (120 min / safe failure mode)
Response time tA
≤ 25 ns
Max. backup fuse with V-type through wiring
80 A (gG)
Max. backup fuse with branch wiring
160 A (gG)
Indicator/remote signaling
Switching function
Changeover contact
Operating voltage
5 V AC ... 250 V AC
Operating voltage
30
Operating current
5 mA AC ... 1.5 A AC
Operating current
1
Connection method
Screw connection
Screw thread
M2
Tightening torque
0.25 Nm
Stripping length
7
Conductor cross section flexible
0.14 mm² ... 1.5 mm²
Conductor cross section solid
0.14 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Connection data
Screw thread
M5
Tightening torque
4.5 Nm (1.5 mm² ... 16 mm²)
Tightening torque
4.5 Nm (25 mm² ... 35 mm²)
Stripping length
16
Conductor cross section flexible
1.5 mm² ... 25 mm²
Conductor cross section solid
1.5 mm² ... 35 mm²
Conductor cross section AWG
15 ... 2
UL specifications
SPD Type
1
Maximum continuous operating voltage MCOV (L-L)
350
Maximum continuous operating voltage MCOV (L-N)
350 V (120/240S)
Maximum continuous operating voltage MCOV (L-G)
175
Maximum continuous operating voltage MCOV (N-G)
175 V (120/240S)
Nom. voltage
120/208 V AC (Wye)
Nom. voltage
120/240 V AC (Split phase)
Mode of protection
L-L
Mode of protection
L-G
Power distribution system
Wye
Nominal frequency
50/60 Hz
Voltage protection rating VPR (L-L)
1200
Voltage protection rating VPR (L-N)
1200 V (120/240S)
Voltage protection rating VPR (L-G)
700
Voltage protection rating VPR (N-G)
700 V (120/240S)
Nominal discharge current In
20
Maximum Surge Current per Phase
65
Short-circuit current rating (SCCR)
200
UL indicator/remote signaling
Operating voltage
125
Operating current
1 A AC
Tightening torque
2 lbf-in. ... 4 lbf-in.
Conductor cross section AWG
30 ... 14
UL connection data
Conductor cross section AWG
10 ... 2
Tightening torque
30
Standards and Regulations
Standards/regulations
IEC 61643-11 2011
Standards/regulations
EN 61643-11 2012