Product Description:
MCR temperature transducer for Pt 100 temperature sensors, configured via DIP switch, with screw connection, not pre-configured

GTIN
: 04017918956561
Series
: MINI MCR-SL-PT100-UI-NC
Type
: Weerstandsthermometer-meetwaardeomv
Key Features
- MCR temperature transducer for Pt 100 temperature sensors
- configured via DIP switch
- with screw connection
- not pre-configured
Advantages
• Power supply possible via the foot element (TBUS)
• For 2-, 3-, 4-conductor Pt 100 sensors in accordance with IEC 60751
• Error indication via diagnostic LED and analog signal
• Input and output signals can be configured via DIP switches
• Highly-compact temperature transducer for electrical isolation, conversion, amplification, and filtering of
• 3-way isolation
• Pt 100 signals to create standard signals
• Temperature measuring range of -150°C to +850°C
Training Data Goes here
Dimensions
Width
6.2 mm
Height
93.1 mm
Depth
101.2 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 65 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Degree of protection
IP20
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Input data
Configurable/programmable
Yes
Sensor types (RTD) that can be used
Pt 100 (IEC 60751/EN 60751)
Sensor input current
1 mA (constant)
Connection technology
2-, 3-, 4-conductor
Output data
Number of outputs
1
Configurable/programmable
Yes, unconfigured
Voltage output signal
0 V ... 10 V
Voltage output signal
10 V ... 0 V
Voltage output signal
0 V ... 5 V
Voltage output signal
1 V ... 5 V
Current output signal
0 mA ... 20 mA
Current output signal
4 mA ... 20 mA
Current output signal
20 mA ... 0 mA
Current output signal
20 mA ... 4 mA
Max. output voltage
approx. 12.5 V
Max. output current
23
Short-circuit current
approx. 10 mA
Load/output load voltage output
≥ 10 kΩ
Load/output load current output
< 500 Ω (at 20 mA)
Ripple
< 20 mVPP (at 10 kΩ)
Ripple
< 20 mVPP (at 500 Ω)
Power supply
Nominal supply voltage
24
Supply voltage range
19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Max. current consumption
< 21 mA (at 24 V DC)
Power consumption
< 500 mW
Connection data
Connection method
Screw connection
Stripping length
12
Screw thread
M3
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
26 ... 12
General
No. of channels
1
Transmission error in the set measuring range
((100 K / set measurement range [K]) + 0.1)%
Transmission error in the full measuring range
≤ 0,2 %
Maximum temperature coefficient
< 0.02 %/K
Protective circuit
Transient protection
Electrical isolation
Basic insulation according to EN 61010
Overvoltage category
II
Degree of pollution
2
Rated insulation voltage
50 V AC/DC
Test voltage, input/output/supply
1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Color
green
Housing material
PBT
Mounting position
any
Assembly instructions
The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
EMC data
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
10
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Standards and Regulations
Connection in acc. with standard
CUL
Standards/regulations
EN 61000-4-2
Standards/regulations
EN 61000-4-5
Conformance/approvals
Designation
CE
Certificate
----
Designation
UL, USA/Canada
Identification
UL 508 Recognized
Identification
Class I, Div. 2, Groups A, B, C, D T5
Designation
Shipbuilding approval
Certificate
DNV GL TAA00002R0
Temperature
B
Humidity
B
Vibration
B
EMC
A
Enclosure
Required protection according to the Rules shall be provided upon installation on board
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years