Phoenix Contact Resistance thermometer measuring transducer - MINI MCR-2-RTD-UI-PT - 2902052
Product Description:
Configurable temperature transducer with plug-in connection technology for connecting 2, 3, and 4-conductor resistance thermometers and resistance-type sensors. Configurable via DIP switch or software. push-in connection technology, standard configuration

GTIN
: 04046356652094
Series
: MINI MCR-2-RTD-UI-PT
Type
: Weerstandsthermometer-meetwaardeomv
Key Features
- Configurable temperature transducer with plug-in connection technology for connecting 2
- and 4-conductor resistance thermometers and resistance-type sensors
- Configurable via DIP switch or software
- standard configuration
Training Data Goes here
Dimensions
Width
6.2 mm
Height
109.81 mm
Depth
119.2 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Degree of protection
IP20 (not assessed by UL)
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Input data
Configurable/programmable
Yes
Sensor types (RTD) that can be used
Pt, Ni, Cu sensors
Linear resistance measuring range
0 Ω ... 4000 Ω (Minimum measuring span: 10% of the selected measuring range)
Sensor input current
approx. 200 µA
Temperature measuring range
-200 °C ... 850 °C (Range depends on sensor type, range can be set freely via software or in increments from -150°C to 850°C via DIP switches)
Connection technology
2-, 3-, 4-conductor
Output data
Number of outputs
1
Voltage output signal
0 V ... 5 V (via DIP switch)
Voltage output signal
1 V ... 5 V (via DIP switch)
Voltage output signal
0 V ... 10 V (via DIP switch)
Voltage output signal
10 V ... 0 V (via DIP switch)
Voltage output signal
0 V ... 10.5 V (can be set via software)
Current output signal
0 mA ... 20 mA (via DIP switch)
Current output signal
4 mA ... 20 mA (via DIP switch)
Current output signal
20 mA ... 0 mA (via DIP switch)
Current output signal
20 mA ... 4 mA (via DIP switch)
Current output signal
0 mA ... 21 mA (can be set via software)
Max. output voltage
approx. 12.3 V
Max. output current
24.6 mA
Short-circuit current
< 31.5 mA
Load/output load voltage output
≥ 10 kΩ
Load/output load current output
≤ 600 Ω (at 20 mA)
Ripple
< 10 mVrms
Ripple
< 10 mVrms (at 600 Ω)
Power supply
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Typical current consumption
32 mA (24 V DC)
Typical current consumption
63 mA (12 V DC)
Power consumption
≤ 850 mW (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)
Connection data
Connection method
Push-in connection
Stripping length
10
Conductor cross section solid
0.2 mm² ... 2.5 mm² (with ferrule)
Conductor cross section solid
0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12 (flexible)
General
Transmission error resistance thermometer
0.1 % * 350 K / set measuring range; 0.1 % > 350 K (Pt/Ni)
Transmission error resistance thermometer
0.3 % * 200 K / set measuring range; 0.3 % > 200 K (Cu)
Transmission error resistance-type sensor
2
Maximum temperature coefficient
0.01 %/K
Protective circuit
Transient protection
Electrical isolation
Reinforced insulation in accordance with IEC 61010-1
Overvoltage category
II
Degree of pollution
2
Rated insulation voltage
300 V (effective)
Test voltage, input/output/supply
3 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Housing material
PBT
Mounting position
any
Assembly instructions
The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
EMC data
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
0.06 %
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
0.1 %
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
0.07 %
Standards and Regulations
Standards/regulations
EN 61000-4-2
Standards/regulations
EN 61000-4-5
Conformance/approvals
Designation
CE
Certificate
----
Designation
ATEX
Identification
II 3 G Ex nA IIC T4 Gc X
Designation
UL, USA/Canada
Identification
UL 508 Listed
Identification
Class I, Div. 2, Groups A, B, C, D T6
Identification
Class I, Zone 2, Group IIC T6
Designation
Shipbuilding approval
Identification
C, EMC2
Certificate
DNV GL 14445-15HH
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years