Primary-switched TRIO POWER power supply for DIN rail mounting, input: 1-phase, output: 24 V DC/5 A

GTIN
: 04046356046640
Series
: TRIO-PS/1AC/24DC/5
Type
: Voeding
Key Features
- Primary-switched TRIO POWER power supply for DIN rail mounting
- input: 1-phase
- output: 24 V DC/5 A
Advantages
• Use the third negative terminal block as a grounding terminal block and minimize installation costs
• Rugged design with metal housing and wide temperature range from -25 to +70°C
• Maximum operational reliability thanks to high MTBF (mean time between failures) of more than 500,000 hours and high dielectric strength of up to 300 V AC
• Compensation of voltage drops by means of output voltage that can be adjusted on the front
Training Data Goes here
Dimensions
Width
40
Height
130
Depth
115
Installation distance right/left
0 mm / 0 mm
Installation distance top/bottom
50 mm / 50 mm
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Climatic class
3K3 (in acc. with EN 60721)
Degree of pollution
2
Input data
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range
85 V AC ... 264 V AC (Derating < 90 V AC: 2,5 %/V)
Dielectric strength maximum
300
AC frequency range
45 Hz ... 65 Hz
Discharge current to PE
< 3.5 mA
Current consumption
1.65 A (120 V AC)
Current consumption
0.9 A (230 V AC)
Nominal power consumption
189
Inrush current
< 15 A
Mains buffering time
> 20 ms (120 V AC)
Mains buffering time
> 110 ms (230 V AC)
Input fuse
3.15 A (slow-blow, internal)
Recommended breaker for input protection
6 A ... 16 A (Characteristics B, C, D, K)
Power factor (cos phi)
0.72
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
24 V DC ±1 %
Setting range of the output voltage (USet)
22.5 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)
5 A (UOUT = 24 V DC)
Derating
55 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
yes
Feedback voltage resistance
35
Protection against overvoltage at the output (OVP)
< 35 V DC
Max. capacitive load
unlimited
Active current limitation
Approx. 10 A (for short-circuit)
Control deviation
< 1 % (change in load, static 10 % ... 90 %)
Control deviation
< 2 % (change in load, dynamic 10 % ... 90 %)
Control deviation
< 0.1 % (change in input voltage ±10 %)
Residual ripple
< 20 mVPP
Output power
120
Typical response time
< 1 s
Peak switching voltages nominal load
< 30 mVPP
Maximum power dissipation in no-load condition
1.1 W
Power loss nominal load max.
18
General
Net weight
0.6 kg
Operating voltage display
Green LED
Efficiency
89 % (for 230 V AC and nominal values)
MTBF (IEC 61709, SN 29500)
> 2031000 h
Insulation voltage input/output
4 kV AC (type test)
Insulation voltage input/output
2 kV AC (routine test)
Insulation voltage input / PE
2 kV AC (type test)
Insulation voltage input / PE
2 kV AC (routine test)
Insulation voltage output / PE
500 V DC (type test)
Protection class
I (with PE connection)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
alignable: horizontally 0 mm, vertically 50 mm
Connection data, input
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
9
Screw thread
M2,5
Signaling
Status display
"DC OK" LED green
Note on status display
UOUT > 21.5 V: LED lights up
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Noise immunity
EN 61000-6-2:2005
Connection in acc. with standard
CUL
Standards/regulations
EN 61000-4-2
Contact discharge
4 kV (Test Level 2)
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
10
Frequency range
1.4 GHz ... 2 GHz
Test field strength
3
Standards/regulations
EN 61000-4-4
Comments
Criterion B
Standards/regulations
EN 61000-6-3
Standards/regulations
EN 61000-4-6
Frequency range
0.15 MHz ... 80 MHz
Voltage
10 V (Test Level 3)
Standards/regulations
EN 61000-4-11
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
EN 60950-1 (SELV)
Standard – Safety extra-low voltage
EN 60204 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment
EN 50178
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Shipbuilding approval
DNV GL (EMC A)
UL approvals
UL/C-UL listed UL 508
UL approvals
UL/C-UL Recognized UL 60950-1
Shock
15g in all directions in acc. with IEC 60068-2-27
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Vibration (operation)
15 Hz ... 150 Hz, 2.3g, 90 min.
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;