Product Description:
MCR current transducer, programmable and configurable, for measuring direct, alternating and distorted currents, input current 0...0.2 to 0...11 A, unconfigured

GTIN
: 04017918169275
Series
: MCR-S-1-5-UI-DCI-NC
Type
: Stroommeetwaardeomvormer
Key Features
- MCR current transducer
- programmable and configurable
- for measuring direct
- alternating and distorted currents
- input current 0...0.2 to 0...11 A
- unconfigured
Advantages
• True r.m.s. value measurement
• Device can be set via DIP switches or MCR/PI-CONF-WIN configuration software
• 3-way isolation
Training Data Goes here
Dimensions
Width
22.5 mm
Height
99
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Maximum altitude
< 2000 m
Degree of protection
IP20
Noise immunity
EN 61000-6-2
Input data
Input
Current measuring input
Number of inputs
3
Configurable/programmable
Yes, unconfigured
Input current range
0 A ... 11 A (AC/DC)
Operate threshold
2 % (of measuring range nominal value 1/5/10 A)
Setting range for min. input current
0 A ... 200 mA
Setting range for max. input current
0 A ... 11 A
Impulse form
AC, DC or distorted currents
Overload capacity
2 x IN (continuous)
Surge strength
20 x IN (1 s)
Frequency measuring range
15 Hz ... 400 Hz
Connection method
Screw connection
Output data
Output name
Voltage output / current output
Voltage output signal
0 V ... 10 V
Voltage output signal
2 V ... 10 V
Voltage output signal
-10 V ... 10 V
Voltage output signal
0 V ... 5 V
Voltage output signal
1 V ... 5 V
Voltage output signal
-5 V ... 5 V
Voltage output signal
10 V ... 0 V
Voltage output signal
10 V ... 2 V
Voltage output signal
10 V ... -10 V
Voltage output signal
5 V ... 0 V
Voltage output signal
5 V ... 1 V
Voltage output signal
5 V ... -5 V
Current output signal
0 mA ... 20 mA
Current output signal
4 mA ... 20 mA
Current output signal
20 mA ... 0 mA
Current output signal
20 mA ... 4 mA
Load/output load voltage output
> 10 kΩ
Load/output load current output
< 500 Ω
Switching output
Output name
No switching output
Power supply
Supply voltage range
20 V DC ... 30 V DC
Max. current consumption
< 40 mA (without load)
Connection data
Stripping length
8
Screw thread
M3
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
General
Maximum transmission error
< 0.5 % (of nominal range value under nominal conditions)
Temperature coefficient, typical
< 0.025 %/K
Step response (10-90%)
330 ms (with AC)
Step response (10-90%)
40 ms (with DC)
Status display
Green LED
Overvoltage category
III
Degree of pollution
2
Rated insulation voltage
300 V AC (to earth)
Test voltage input/output
4 kV (50 Hz, 1 min.)
Test voltage input/power supply
4 kV (50 Hz, 1 min.)
Test voltage output/power supply
500 V (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Color
green
Housing material
Polyamide PA non-reinforced
Mounting position
any
Standards and Regulations
Connection in acc. with standard
CUL
Low Voltage Directive
Conformance with Low Voltage Directive
Conformance
CE-compliant
UL, USA/Canada
Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X
UL, USA/Canada
Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only
Conformance/approvals
Designation
CE
Identification
CE-compliant
Designation
UL, USA/Canada
Identification
Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X
Identification
Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years